User Guide
Table Of Contents
Programming Occupied & Unoccupied Periods
PROGRAMMING TIPS
Page 13
If only the Occupied 1 period is selected in the first programming 
step (page 9), Occupied 2 &  3 programming steps are skipped.  
Furthermore, if Occupied 2 is selected, Occupied 3 programming 
steps are skipped.
Heat & Cool setpoints for Occupied 1 are the same for every day of 
the week. If desired, Heat & Cool setpoints for Occupied 2 & 3 can 
be adjusted differently for each day of the week.
If the start time is set later in the day than the stop time, the 
program will run from the start time to midnight and from midnight 
to the stop time on the same day.  For example:  9pm start, 8am 
stop, on Monday. In this example the program will run from 12am 
Monday  to  8am  Monday  and  again  from  9pm  Monday  to  12am 
Tuesday. 
Unoccupied Operation: The unoccupied settings take effect at 
all times when: (1) the program is on and (2) the current time is 
outside a preset occupied period. For this reason start and stop 
times are not necessary for unoccupied time periods.
If the same start and stop times are programmed for an occupied 
period, then it will run 24 hours.
If  one  occupied  period  starts  and  stops  within  another  occupied 
period the lower occupied # has priority.  For example:  If Occupied 
3 is programmed to be on for 24 hours, and Occupied 2 is program-
med to run that day, then the Occupied 2 setting will take over for 
Occupied 3 between Occupied 2 start and stop times.