About Advanced Features & Operation
CLOCK BACKUP - In the event of a power loss, the thermostat’s internal 
 clock will continue to keep proper time for a minimum of 48 hours without
 external power or batteries.
DEADBAND OPERATION - Controls up to two Heat and two Cool stages
 (please see the diagram on the next page).
And
 The 2nd Stage of heat or cool is turned on when:
 (A) The 1st Stage has been on for a minimum of two minutes.
 (B) The temperature spread from the setpoint is equal to or greater
 than: the setpoint plus the 1st stage deadband (step #7, page 16), 
 plus the 2nd stage deadband. This 2nd stage deadband is fixed at 
 two degrees and is not adjustable. 
 The 1st Stage of heat or cool is turned on when:
 (A) The temperature spread from the setpoint is equal to or greater
 than: the setpoint plus the 1st stage deadband (step #7, page 16), 
 This 1st stage deadband is adjustable from 1-6 degrees and the 
 default is two degrees. 
88
88
88
unoccupied
Program
Fan On
Service Filter
On
Am
Pm
COOL
HEAT
Override
Locked
ONOFF
AUTO
Stop
Start
SetupSuMoTuWeThFrSa
123
I2:00
Page 20
OFF
o
Pm
I2:00
Mo
OFF
o
Pm
I2:00
Mo
o
CALIBRATION - Under normal circumstances it will not be necessary to 
 adjust the calibration of the temperature. If calibration is required, 
 please contact a trained HVAC technician to correctly perform the 
 following procedure. 
Place the therm-
ostat in the OFF 
mode.
Press 
MODE button. 
While holding the 
MODE button, 
press and hold the 
DOWN button for 
5 seconds. All icons 
will appear on the display.
and hold the 
MODE
Press the MODE 
button once. The 
thermostat temp-
erature will be 
displayed and 
may be calibrated 
using the UP or DOWN buttons.
After calibration is 
complete, press 
the MODE button 
once to save 
your changes and 
return to normal operation.