User Guide
Table Of Contents
CK1
GND
RS
RS+5
W2
Y2
 C
 G
 Y1
W1-O-B
 R
About Advanced Features & Operation
DRY CONTACT SWITCH - 
 Central Time Clock, Occupancy Sensor, or a Telephone activated device 
 to force 1 or more thermostats into Occupied 1. 
This feature allows an external device such as a 
Connect wires to a time 
clock or other device to 
force the thermostat into 
Occupied 1.
Important Note: For control of multiple
thermostats by 1 source, refer to the 
enclosed yellow document P/N 88-175 
‘Potential Phasing Problems’ before 
installation.
The CK1 and GND terminals are ‘normally open.’ When the dry contact 
is energized, shorting CK1 and GND together, the thermostat will be 
forced into Occupied 1 setpoints and the Occupied 1 icon will blink 
(page 9). 
Note: The thermostat must be in Program On mode for this feature to 
have any effect.  
ELECTRIC HEAT - Selecting Electric Heat (
 thermostat to turn on the fan immediately any time there is a heat 
 demand. Since most gas furnaces control the fan, this feature should be 
 off unless it is necessary for the thermostat to energize the fan with first 
 stage heat.
step #6, page 16), will cause the 
The above figure assumes the minimum on time for the prior stage 
has been met to allow the next stage to turn on, once the deadbands 
have been exceeded. 
Heat
Setpoint
Cool
Setpoint
Deadband Deadband DeadbandDeadband
db 1 db 1db 2 db 2
(adj. 1-6 ) (adj. 1-6 )
1st Stage
turn on
2nd Stage
turn on
1st Stage
turn on
2nd Stage
turn on
Heating
Cooling
TEMPERATURE
DECREASE INCREASE
(non-adj. 2 ) (non-adj. 2 )
Page 21