ERV 120 EC Specs

Tel: 888-640-0925
513-348-3853
Fax: 513-268-4597
Sales@ventsus.com
VentsUS.com
11013 Kenwood Road,
Cincinnati, Ohio 45242
PRODUCT SPECIFICATIONS
2021-10
DESCRIPTION
VENTS’ ERV 120 EC are the complete whole house ventilation system
designed to bring a continuous supply of fresh air into the house while
exhausting an equal amount of stale air.
Five year warranty.
CASING
Steel casing is covered with high-quality multilayer aluminium
and zinc alloy to prevent corrosion.
The casing is equipped with a switch to turn the ventilator off
when the service panel is opened.
AIR FILTRATION
Washable MERV 6 air filters in exhaust and supply air streams.
Optional supply: anti grease aluminum filter.
ENERGY RECOVERY CORE
Enthalpic core provides both heat&humidity recovery. For enthalpic
core no drain required.
FANS
High efficient electronically commutated motors with external motor
and impeller with forward curved blades. EC motors are featured with
high performance and total speed controllable range. The electric
motors and impellers are dynamically balanced.
DEFROST SYSTEM
To protect the Energy Recovery Core, an antifreeze electronic protec-
tion system is applied. It switches the supply fan off according to
the temperature sensor settings. Warm extract air defrosts the ERV
core then the supply fan switches on and the ventilator continues
operating under rated conditions.
CONSTANT FLOW
Recirculation or only exhaust defrost modes are available.Frigate ERV
120 EC CF has an automatic constant air flow control function to keep
the air flow in supply and exhaust air ducts constant even in case of
variable air resistance. This function is provided with the integrated
air flow control units. The electronic sensors convert the actual air
flow to the analogue signal that is proportional to the air flow in the
air duct. These signals are transmitted to the controller that controls
the rotation speed of a respective fan in such a way that the actual
rotations speed is equal to the set value.
MANUAL BALANCING
Manual balancing is a standard balancing system. Fan speed man-
ually adjusted by operating on units controller (Built-in control panel
with independent fan speed adjustment 0%-100%).
CONTROL BOARD
The unit incorporates an integrated control system with following
functions:
Operation mode switch.
Airflow balancing enabled by supply and exhaust fan indepen-
dent speed adjustment from 0 to 100% (percentage is displayed
on built in screen).
Automatic recovery core frost protection.
External control device connection (up to 5 at the same time).
Fans speed and temperature
sensor set up buttons
Screen
Terminals to connect external
control devices
Three-position mode switch
SUITABLE FOR:
Bathroom / kitchen / apartments / cottages / small offices.
ENERGY RECOVERY VENTILATION
Frigate ERV 120 EC

Summary of content (3 pages)