USER’S MANUAL HRV 80 (R) (EC) (L) HRV 100 (R) (EC) (L) HRV 120 (R) (EC) (L) HRV 150 (R) (EC) (L) ERV 80 (R) (EC) (L) ERV 100 (R) (EC) (L) ERV 120 (R) (EC) (L) ERV 150 (R) (EC) (L) Heat and energy recovery air handling unit
HRV/ERV 80/100/120/150 (R) (EC) (L) CONTENTS Safety requirements...................................................................................................................................................................... 2 Purpose ................................................................................................................................................................................................ 5 Delivery set...............................................................
UNPACK THE UNIT WITH CARE. WHILE INSTALLING THE UNIT, FOLLOW THE SAFETY REGULATIONS SPECIFIC TO THE USE OF ELECTRIC TOOLS. DO NOT LAY THE POWER CABLE OF THE UNIT IN CLOSE PROXIMITY TO HEATING EQUIPMENT. DO NOT OPERATE THE UNIT OUTSIDE THE TEMPERATURE RANGE STATED IN THE USER’S MANUAL. DO NOT OPERATE THE UNIT IN AGGRESSIVE OR EXPLOSIVE ENVIRONMENTS. DO NOT WASH THE UNIT WITH WATER. PROTECT THE ELECTRIC PARTS OF THE UNIT AGAINST INGRESS OF WATER.
HRV/ERV 80/100/120/150 (R) (EC) (L) POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL. ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
PURPOSE CAUTION! FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS AS WELL AS FLAMMABLE MIXTURES, EVAPORATION OF CHEMICALS, STICKY SUBSTANCES, FIBROUS MATERIALS, COARSE DUST, SOOT AND OIL PARTICLES OR ENVIRONMENTS FAVOURABLE FOR THE FORMATION OF HAZARDOUS SUBSTANCES (TOXIC SUBSTANCES, DUST, PATHOGENIC GERMS). FOR USE IN NON FIRE RATED INSTALLATIONS ONLY. FOR USE IN ONE- AND TWO-FAMILY DWELLINGS ONLY.
HRV/ERV 80/100/120/150 (R) (EC) (L) TECHNICAL DATA The unit is designed for indoor application at ambient temperature from+34 ˚F (+1 ˚C) up to +104 ˚F (+40 ˚C) and relative humidity up to 80 %. Hazardous parts access and water ingress protection rating: • IP 44 for the unit motors • IP 22 for the assembled unit connected to the air ducts The unit design is constantly being improved, so some models may be slightly different from those ones described in this manual. 156 1.
Overall dimensions 9 1/2" 20 13/16" 17" 9 1/2" Frigate HRV/ERV 80 (EC) 3 13/16" Ø 4 7/8" 4 7/16" 18" 9 1/16" 21 15/16" 8 7/16" 4 7 /16" 8 1/4" 20 13/16" 17 3/16" Ø 4 7/8" 3 13/16" 9 1/2" Frigate HRV/ERV 80 R (EC) 4 7/16" 29 1/16" 9 1/16" 25 1/16" 4 3/4" 8 7/16" 12 3/8" 23 7/8" Ø 4 7/8" 1 1/8" 3 9/16" 12 3/8" 13/ " 16 20 1/16" Frigate HRV/ERV 120 (EC) (L) 5 7/8" www.vents-us.
HRV/ERV 80/100/120/150 (R) (EC) (L) Frigate HRV/ERV 120 R (EC) 13/ " 16 3 9/16" Ø 4 7/8" 12 3/8" 23 7/8" 20 1/16" 9/ " 16 5 11/16" 9 5/8" 30 15/16" 34 7/8" 9" 4 3 /16" 4 5/8" 11 13/16" 25 1/8" 21 3/8" 11 13/16" Frigate HRV/ERV 100/150 (EC) (L) Ø 4 7/8" 27 3/4" 9 5/8" 9 1 /8" 31 3/4" 4 5/8" 4 5/8" 8 9 5/8" 25 3/16" 21 3/8" Ø 4 7/8" 36" 39 15/16" 11 13/16" 11 13/16" Frigate HRV/ERV 100/150 R (EC) (L) 9 1/8" 4 5/8" www.vents-us.
UNIT DESIGN AND OPERATING PRINCIPLE The unit operation is as follows: warm polluted air is extracted from indoor to the unit and is cleaned by the extract filter. Then the air streams through the heat recovery core and is removed outside by the extract fan. The cold intake air from outside flows into the unit and is cleaned by the supply filter. Further the air flows through the heat recovery core and is supplied inside by the supply fan.
HRV/ERV 80/100/120/150 (R) (EC) (L) Assembly drawing for Frigate HRV/ERV 80 R (EC) and air flow diagram in heat recovery mode Supply filter Control unit Extract filter Supply fan Extract fan FUSE 1 FUSE SPEED CONTROL LOW FUSE 2 MED 1 2 3 4 5 6 7 8 9 101112 FUSE STANDBY FRESH AIR FROM OUTSIDE STALE AIR FROM ROOM Cross-flow heat recovery core Backdraft damper AIR SUPPLIED TO ROOM UTILIZED EXHAUST AIR Recirculation damper Condensate drain pipe Swivel service panel Assembly drawing for Frigate
Assembly drawing for Frigate HRV/ERV 120 (EC) L and air flow diagram in heat recovery mode Supply filter Extract filter Control unit FUSE 1 FUSE SPEED CONTROL LOW MED FUSE 2 1 2 3 4 5 6 7 8 9 101112 FUSE STANDBY STALE AIR FROM ROOM FRESH AIR FROM OUTSIDE AIR SUPPLIED TO ROOM UTILIZED EXHAUST AIR Cross-flow heat recovery core Extract fan Supply fan Condensate drain pipe Swivel service panel Assembly drawing for Frigate HRV/ERV 100/150 (EC) and air flow diagram in heat recovery mode Extract fan
HRV/ERV 80/100/120/150 (R) (EC) (L) Assembly drawing for Frigate HRV/ERV 100/150 EC L and air flow diagram in heat recovery mode Supply fan Supply filter Extract filter Control unit FUSE 1 Extract fan FUSE SPEED CONTROL LOW MED FUSE 2 1 2 3 4 5 6 7 8 9 101112 FUSE STANDBY STALE AIR FROM ROOM FRESH AIR FROM OUTSIDE AIR SUPPLIED TO ROOM UTILIZED EXHAUST AIR Cross-flow heat recovery core Swivel service panel Condensate drain pipe Assembly drawing for Frigate HRV/ERV 100/150 R (EC) and air flow d
Air flow diagram for Frigate HRV/ERV 80/120/100/150 R (EC) in recirculation mode (the swivel service panel is conventionally not shown) FUSE 1 FUSE SPEED CONTROL LOW MED FUSE 2 1 2 3 4 5 6 7 8 9 101112 FUSE STANDBY FRESH AIR FROM OUTSIDE STALE AIR FROM ROOM UTILIZED EXHAUST AIR AIR SUPPLIED TO ROOM Air flow diagram for Frigate HRV/ERV 80/120/100/150 R (EC) L in recirculation mode (the swivel service panel is conventionally not shown) FUSE 1 FUSE SPEED CONTROL LOW MED FUSE 2 1 2 3 4 5 6 7 8 9
HRV/ERV 80/100/120/150 (R) (EC) (L) INSTALLATION AND SET-UP ALL OPERATIONS DESCRIBED IN THIS USER’S MANUAL MUST BE PERFORMED BY QUALIFIED PERSONNEL ONLY, PROPERLY TRAINED AND QUALIFIED TO INSTALL AND MAINTAIN VENTILATION EQUIPMENT. DO NOT ATTEMPT TO INSTALL THE PRODUCT YOURSELF. IT IS UNSAFE AND IMPOSSIBLE WITHOUT SPECIAL KNOWLEDGE. The units are designed for celling mounting. While installing the unit ensure convenient access for subsequent maintenance and repair.
EACH VENTILATION UNIT MUST BE CONNECTED TO AN INDIVIDUAL U-TRAP IRRESPECTIVELY OF THE VENTILATION UNIT TYPE Condensate drainage The HRV units must be connected to a condensate drain system. The ERV units are equipped with enthalpy recovery cores with no condensate buildup and require no condensate drain system. The drain pan in the heat recovery unit has a drain pipe to remove condensate outside of the unit.
HRV/ERV 80/100/120/150 (R) (EC) (L) CONNECTION TO POWER MAINS POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL. ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY. The unit is for connection to the fixed installation and rated for connection to 120 V/60 Hz power supply source.
CONNECTION OF EXTERNAL CONTROLS The ventilation unit enables connection of maximum 5 controls. If any control unit is activated, the ventilation unit goes to high-speed mode. Connectable controls: 1. Remote control (thermostat). Remote control (thermostat) functions: • Unit on/off • Speed selection • Indoor temperature display • Scheduled operation 2. CO2 sensor. Recommended for use in office buildings and public premises.
HRV/ERV 80/100/120/150 (R) (EC) (L) UNIT CONTROL OPERATION MODES • Permanent low-speed mode or standby mode • High-speed mode The unit has a three-position speed switch. LOW or MED speed are used to set permanent operation mode or to set the STANDBY mode. The external controls switch the ventilation unit to the high-speed mode. The supply and extract fan speed is individually adjusted. The air capacity is controllable from 0 % up to 100 %.
In case of alarm the alarm message «Err» is displayed. To detect the alarm root, press the «KEY1» button and review the list of all alarm messages using the «KEY2» and «KEY3» buttons. The alarm message consists of a number (1, 2, 3) and a letter (n, Y). The number determines the alarm message type. 1: fire alarm activation. 2: temperature sensor short circuit 3: temperature sensor breakout The letter indicates no alarm (n) or available alarm (Y). Example: «1-Y»: fire alarm activation.
HRV/ERV 80/100/120/150 (R) (EC) (L) FREEZE PROTECTION OF THE HEAT RECOVERY CORE The freeze protection function prevents freezing of the heat recovery core in the cold season. This function is activated automatically and cannot be turned on or off. The ventilation unit periodically switches from rated operation mode to the special defrost mode (the extract fan runs in high speed, the supply fan is off ) and vice versa according to the signaling from the outdoor temperature sensor.
TECHNICAL MAINTENANCE WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: BEFORE REMOVING THE FILTERS, SWITCH OFF THE EXTERNAL AUTOMATIC CIRCUIT BREAKER AND LOCK THE SERVICE DISCONNECTING MEANS, THEN OPEN THE HINGED SERVICE PANEL AND REMOVE THE FILTERS CAREFULLY. IT IS POSSIBLE TO CLEAN FILTERS WITH A VACUUM CLEANER OR RINSE THEM WITH WATER AND DRY. MAKE SURE FILTERS ARE COMPLETELY DRY BEFORE THEY HAVE BEEN INSTALLED BACK INTO THE UNIT.
HRV/ERV 80/100/120/150 (R) (EC) (L) 2. Recovery core maintenance (once per year). Some dust may accumulate on the recovery core even in case of regular maintenance of the filters. Regular cleaning is required to maintain the high recovery efficiency. To clean the recovery core pull it out of the unit and clean it with a vacuum cleaner. Optionally cleaning with warm detergent solution is allowed.
Trouble The fan(s) do(es) not get started during activation of the unit. The unit does not get started, the indicator displays Err. Troubles and troubleshooting Possible reasons Troubleshooting Make sure the power supply line is connected correct. No power supply. Otherwise troubleshoot a connection error. Turn the unit off. Troubleshoot the motor jamming. Jammed motor, soiled impeller blades. Clean the blades. Restart the unit. System failure. Contact the product Seller.
HRV/ERV 80/100/120/150 (R) (EC) (L) STORAGE AND TRANSPORTATION REGULATIONS • • • • • • • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +4 ˚F (+5 ˚C) to +104 ˚F (+40 ˚C) and relative humidity up to 70 %. Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
www.vents-us.
HRV/ERV 80/100/120/150 (R) (EC) (L) 26 www.vents-us.
CERTIFICATE OF ACCEPTANCE Unit Type Heat and energy recovery air handling unit Model Serial Number Manufacture Date Quality Inspector’s Stamp SELLER INFORMATION Seller Address Phone Number E-mail Purchase Date This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
VUSA172-1EN-06