FRIGATE ERV Installation Guide

www.vents-us.com
MIU_35_50_ERV+HRV-01
Vents-US
400 Murray Road, Cincinnati, OH 45217, USA
Tel: 1-888-640-0925, 513-583-5786, Fax: 513-268-4597
E-mail: support@ventsus.com
Wall unit mounting
Mark holes on the wall. Drill the holes and insert the expansion anschors.
Install the mounting bracket. Install the unit on the mounting bracket.
Tighten the triangular xing screws on the mounting bracket.
Attach the wall mounting bracket to the wall considering the wall material and the unit weight!
Belts, threaded rods and expansion anchors are not included in the delivery package !
The Vents Frigate HRV unit is equipped with a condensate drain hose for condensate drainage.
Connect the drain hose (1), U-trap (3) and drain system (5) with metal, plastic or rubber pipes (2 and 4). The pipes must be sloped down at least by 3°. Before
starting operation of the unit fill the system with water and check that U-trap is always filled with water. Make sure that the water drainage is correct, otherwise
some condensate may be accumulated inside the unit and provoke subsequent equipment damage and water ingress to the room. The condensate drainage system
is designed for operation at the ambient temperature above 32 ºF. If the ambient temperature is below 32 ºF, insulate the drain system and provide air heating.
min 3°
1
3
5
2
4