PERFORMANCE
EXTERNAL STATIC PRESSURE NET SUPPLY AIR FLOW
GROSS AIR FLOW
POWER
SUPPLY EXHAUST
Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts
25 0.1 40 85 41 87 39 83 72
50 0.2 36 76 36 76 34 72 72
75 0.3 31 66 31 66 28 59 72
100 0.4 25 53 26 55 22 47 71
125 0.5 20 42 20 42 17 36 70
SOUND
1.4 Sones (30 L/s @ 0.2 in. W.G.)
Ext. Dierential Pressure - in. W.G.
0
0.1
0.2
0.3
0.4
0.5
0.6
010203040506070809
0100
Gross Airflow -CFM
Supply
Exhaust
Temp
Mode
Supply Temperature Net Airflow
Average
Power
Sensible
Recovery
Efficiency
Adjusted Sensible
Recovery Efficiency
Latent Recovery/
Moisture Transfer
Total Recovery
Efficiency
Adjusted
Total Recovery
Efficiency
°C °F L/s cfm (Watts)
SRE (%)
ASRE (%) LRMT (%) TRE (%) ATRE (%)
HEATING
0 32 20 42 38 64 70 0.36
0 32 24 51 42 64 70 0.33
0 32 28 59 48 63 68 0.31
COOLING
35 95 20 42 40 0.36 39 43
35 95 24 51 48 0.32 37 40