Installation Instructions
5
Temperature [º С] -30...+60 º С (-22 ºF...140 ºF)
Relative humidity [%] 80%
Service life
Warranty service life is 2 years
Operating service life is 5 years
Table 2
The maximum allowable air parameters for the paper heat recovery core are stated in the
table 2.
Model
Speed
Volts
Max. Watts
Max. Amps
RPM
Airow CFM (L/s)
Eciency of heat
exchanger, %
Duct Dia.
Sones
0,1”
(25Pa)
0,2”
(50Pa)
0,3”
(75Pa)
0,4”
(100Pa)
0,5”
(125Pa)
0,6”
(150Pa)
0,7”
(175Pa)
0,8”
(200Pa)
0,9”
(225Pa)
1,0”
(250Pa)
1,2”
(300Pa)
1,4”
(350Pa)
HRV 100DS
ERV 100DS
TRV 100DS
high
120V,
60Hz
139 1,2
3040
120
(57)
115
(54)
109
(51)
98
(46)
88
(42)
77
(36)
65
(31)
52
(25)
38
(18)
24
(11)
-
(-)
-
(-)
<80%
5”
2.8
low
68 1,03
1520
56
(26)
45
(21)
34
(16)
17
(8)
-
(-)
-
(-)
-
(-)
-
(-)
-
(-)
-
(-)
-
(-)
-
(-)
<80%
0.4
HRV 150DS
ERV 150DS
TRV 150DS
high
120V,
60Hz
215 1,83
3040
150
(71)
148
(70)
144
(68)
136
(64)
128
(60)
120
(57)
111
(52)
101
(48)
91
(43)
79
(37)
53
(25)
23
(11)
<80%
5”
2.8
low
95 1,5
1520
77
(36)
70
(33)
63
(30)
53
(25)
43
(20)
33
(16)
22
(10)
-
(-)
-
(-)
-
(-)
-
(-)
-
(-)
<80%
0.4
Table 1
SAFETY REQUIREMENTS
While operating and mounting unit fulll the requirements of the present operation manual
as well as general requirements of all applicable codes and standards valid in USA and Canada.
Ground the unit!
Before connecting the unit to power mains make sure that the unit is free of any visible
damages or any other foreign objects inside the casing that can damage the impeller blades.
Connection of the unit to power mains by duly qualied and authorized electricians only!
Warning!
Mounting, servicing, connection and repair works of the unit are allowed after
the unit is disconnected from power mains.