CONDENSATE DRAINAGE
Fig. 4. Wall unit mounting
The Vents Frigate HRV 100 (150) DS and Vents Frigate TRV 100 (150) DS units are equipped
with a condensate drain hose for condensate drainage (g. 5). Connect the drain hose (1), U-trap (3)
and drain system (5) with metal, plastic or rubber pipes (2 and 4). The pipes must be sloped down at
least by 3°. Before starting operation of the unit ll the system with water and check that U-trap is
always lled with water. Make sure that the water drainage is correct, otherwise some condensate
may be accumulated inside the unit and provoke subsequent equipment damage and water ingress
to the room. The condensate drainage system is designed for operation at the ambient temperature
above 32 ºF (0 °С). If the ambient temperature is below 32 ºF (0 °С), insulate the drain system and
provide air heating.
min 3°
1
3
5
2
4
g. 5. Condensate drainage
This installation example is applicable only
for Vents Frigate ERV 100 DS and Vents
Frigate ERV 150 DS