Installation Manual

30 31
Restoring Factory Settings
If there are reported errors or conguration issues, the user may restore factory
settings to return the thermostat to its default parameters.
Procedure
Power down the thermostat by either removing the batteries or cutting power
to the thermostat;
Remove the faceplate of the thermostat;
Press and hold the CONFIG button located on the control board inside the
thermostat while simultaneously powering the thermostat;
Release the CONFIG button once the thermostat powers up;
If the master reset was successful, the thermostat will display 12:00 and the
thermostat must be re-congured. Please refer to pages 14-22 of this manual.
Contact Verdant technical support if the issues are not resolved.
Troubleshooting Guide APPENDIX 1 - Energy Saving Presets
Level
0
Level
1
Level
2
Level
3
Level
4
Level
5
Fan Control Mode AUTO AUTO AUTO AUTO AUTO AUTO
1st Stage Differential Heat 0.5 0.5 0.5 0.5 0.5 0.5
2nd Stage Differential Heat 1 1 1 2 2 2
1st Stage Differential Cool 0.5 0.5 0.5 0.5 0.5 0.5
Guest Occupancy Threshold
0 5 5 5 5 5
Night Occupancy Threshold 1 1 1 1 1 1
Force 2nd Stage Heating After 30 30 30 30 30 30
Night Occupancy Start 18 19 20 21 22 23
Night Occupancy End 12 11 10 9 8 7
Recovery Time 0 15 20 25 30 0
Recovery Temperature Heat 70 69 68 67 66 65
Setback Delay - Heat 0 30 25 20 15 10
Minimum Setback Temperature 67 66 65 64 63 62
Setback Delay - Cool 0 30 25 20 15 10
Maximum Setback Temperature 72 74 76 78 80 82
Recovery Temperature Cool 71 72 73 74 75 76
Minimum Set point 64 64 65 66 67 68
Maximum Set point 82 82 80 78 76 74
Temperature Control Mode AUTO AUTO AUTO AUTO AUTO AUTO
Auto Changeover Set Point Offset
Dead Band)
1 1 1 1 1 1
Auto Restore OFF ON ON ON ON ON
Setback Set Points OFF ON ON ON ON ON
Automatic Humidity Control ON ON ON ON ON ON
Temperature Calibration 0 0 0 0 0 0