Specifications
36  MONITOR ISM™/AFx™ IP Connectivity Guide  22-9058 v2.1 
4.3.2 Use of Remote IP Address 
and Remote Port Settings 
In order to initiate a call from a main panel 
LCD keypad to a Director PC as described in 
section 2.1.1, the IP Interface Module must 
know where to call. 
Start the IP Module configuration program and 
establish a connection with the IP Module. 
Start-up and log into Director software on the 
same PC that connects with the IP module. 
Obtain the Static (fixed) Remote IP address of 
the PC that the Director operates on. 
Quick Method: 
You can view the 'Subnet Mask' and 'Default 
Gateway' (and IP address of the PC) by 
going to a PC on the same LAN segment as 
the IP Interface board, opening a 
DOS/command prompt, and typing "ipconfig". 
To make sure the PC IP Address is Static 
(fixed): 
Go to Start / Settings / Control Panel / 
Network and Dial-up Connections / Local Area 
Connection / Properties / Internet Protocol 
(TCP/IP). In the “General” window, “Use the 
following IP address” should be checked and 
indicate the PC’s IP address. This is the 
Remote IP address. Make a note of what it is. 
NOTE: If “Obtain an IP address automatically” 
is checked instead and IP address is blank, 
the PC does not have a Static IP address. It 
uses a Dynamic address each time the PC 
goes on line with the network. This is not 
recommendable for remote dial-up because 
every time the PC goes off the network and 
back on again, it is assigned a random IP 
address so it is always changed and would 
not stay the same for the IP Interface Module 
to depend on to call. 
Obtain the Remote IP Port # from Director 
Communications Program (Port Configuration) 
as described in Sect. 2.4.1. 
In the Director program, go to Account 
Folders / select the desired Account / 
Configuration / Panel Group / Panel / System / 
Communication / Director Configuration 
(Telco) / Phone number:
 and type “000” (this 
informs Director that it is not an external 
modem calling). In the nearby Connection 
type: box, select “Incoming and Outgoing IP 
Calls”. Save. 
Multiple IP Devices on a PC: The IP Device 
must be the one referenced in the 
"Communications Pool" for the "Panel Group" 
associated with the specific panel connection.  
See Sect: 2.4.3. 
In the IP Module config program, press the 
ISM tab. Under Setup, enter in the Remote IP 
box the static IP address obtained from the 
Director PC. In the Remote Port box, the 
Remote Port # from the Director’s Port 
Configuration screen. Download these new 
settings to the IP Interface Module. 
Now when a call is initiated from a main panel, 
pressing the X key four times, followed by the 
Service ID and Service User Code, the panel 
will call the Director PC by way of IP and the 
Director will answer. 
For a panel to automatically transmit events / 
alarms to the Director PC/software (Host 
Reporting): 
•  In Panel / Configuration / System / 
Communications / Host Connection – set 
Reporting mode
 to “256 events” and 
Connection type
 to Incoming and Outgoing 
IP Calls.