Specifications
4  MONITOR ISM™/AFx™ IP Connectivity Guide 
22-9058 v2.1 
1.3 Power 
Considerations 
AC power to the Control unit is 16VAC, 
using a 37-40 VA Transformer. 
Exception: 
European cabinets may include a 230V to 16V toroidal 
transformer. 
Each main panel can provide up to 750 mA 
for all loads (modules/SNAPP bus, plus 
auxiliary power connections). 
Expansion modules typically draw 150 mA 
(excluding door and elevator controllers--which 
normally include a dedicated power supply)
. The 
host IP interface board draws 250 mA, and 
slave boards draw 75 mA. Adding power 
supplies for the IP boards is 
recommended. 
Devices should be clustered together, and 
situated close to the power supply. Otherwise 
additional power supplies should be added. (Use 
a multi-meter to ensure adequate voltage is 
available at each device (at least 12.5 volts to 
allow for reasonable battery backup operation 
during a power failure). Current loss due to cable 
length/overloading can also cause failures. 
Exception: Elevator controller and Multi-Tenant 
Apartment Security System keypad installations 
include unique power and cabling aspects.  
Always refer to the installation instructions 
provided with each device. 
Note: For multi-door controller cabinets and 
other heavy-load cabinets that include their own 
power supplies, the Module Bus (+12) line should 
be treated as a 'pass-through' type of connection 
only, with only the Module Bus A, B, and (  − ) 
lines connecting to the devices inside the 
cabinet. 
Peripheral devices that draw current, such as 
smoke detectors and motion detectors should be 
powered from the module they are connected to 
– rather than from the control panel auxiliary 
power terminals. 
1.4 Grounding 
System cabinets must each be connected 
to a locally approved earth ground using 18 
AWG (or heavier) stranded wire. 
The cable shield for any RS-485 links must 
be earth grounded at the main panel, and 
spliced together at all junction points (to 
distribute the shield ground to all sections of 
the cable). It must not be terminated 
anywhere else.










