Specifications
22-0375 rev1.1  Monitor ISM/xL™ Hardware Guide  55 
LEDs 
AC Mains On (green) – on with electrical present. 
Power ON (green) – on if Auxiliary DC power is present 
Trouble (yellow) Normal = not on. – will flash on and off for: 
•  AC Mains failure. 
•  Battery loss. 
•  Module Bus (SNAPP) not active. 
– turns on solid if one or more of the board tampers are active. 
Processor OK 
– normally will flash on and off slowly. 
– will flash on and off rapidly when VBUS is present. 
Relay Trouble Output 
– will change state with any trouble mentioned above present. 
Power Supply Selection Jumpers P4 to P10 
Jumpers Power Supply Type 
and other selections 
P4 P5 P6 P7 P8 
Module Bus(SNAPP) and VBUS Master 
(P9 and P10 are ignored) 
IN IN       
VBUS Slave 
(set P9 and P10 Slave Address) 
IN OUT       
Module Bus (SNAPP) ONLY  OUT  IN       
Stand Alone, no Module Bus or VBUS  OUT  OUT       
110V Operation      IN     
220V Operation      OUT     
Relay Test – disconnect the module bus (SNAPP). Momentarily insert P7 
jumper and remove again. Relay will cycle on, off for 10 secs.
  OUT  
Defeat Battery – where a standby battery is not required, insert P8 jumper 
and the system will ignore battery monitoring. 
IMPORTANT: This jumper must 
be left 
OUT for battery monitoring. 
   OUT 
Module Bus (SNAPP)
VBUS VBUS
Main 
Control 
Unit
MASTER – P4, P5 in
SLAVE – P4 in, P5 out
SNAPP only – P4 off, P5 in
Stand Alone – P4, P5 out 
Master Unit communicating 
to the main control unit on 
the Module Bus. The Module 
Serial # on its sticker is 
programmed into the Module 
Program Section. 
– P4 & P5 in
– P9, P10 ignored
Slave unit # 1 on Master 
Unit’s VBUS. The Module 
Serial # on its sticker is 
ignored. 
– P4 in, P5 out.
– P9, P10 out = Address 0 
or Slave #1 
Slave unit # 2 on Master 
Unit’s VBUS. The Module 
Serial # on its sticker is 
ignored. 
– P4 in, P5 out.
– P9 out, P10 in = Address 
1 or Slave #2 
Parallel 
Connections.
Module Power Supply
0V and VBUS. 
A 12VDC 
connection is 
not needed.
VBUS
VBUS
SNAPP
Module Power Supply
Module Power Supply
VBUS
NOTE: VBUS is an internal communication bus that related VBUS modules 
are used with. The VBUS is not intended for external use. It has been 
designed to be used in a protected enclosure with adjoining interconnection 
between modules in the same enclosure. It communicates with the main 
control over the Module Bus (SNAPP) which is for external communications.
Jumpers  Power Supply 
Slave Address
P9 P10 
1 OUT OUT 
2 OUT IN 
3 IN OUT 
4 IN IN 