Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Averaging Temperature Sensors
Installer’s Specifications
Wiring 22AWG; 2-wire:RTD/Thermistor
Linitemp:
Input Power 5 to 30VDC
Output 1µA/°C or 10mVC
Operating Temperature -25° to 105°C (-13° to 221°F)
Accuracy Calibration Error: 1.5°C (35°F) typical; 2.5°C (37°F) max. at 25°C (77°F)*
Error over Temperature: 1.8°C typical (35°F); 3.0°C (34°F) max.
over 0° to 70°C (32° to 158°F) range
2.0°C (35°F) typical, 3.5°C (38°F) max.
over -25° to 105°C (-13° to 221°F) range
*Room temperature error documented on each unit.
TA SerieS TA SerieS
Dimensions
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
Read and understand the instructions before installing
this product.
Turn off all power supplying equipment before working on it.
The installer is responsible for conformance to all applicable codes.
ProDuct iDentification
quick install
Drill a 1 3/16” diameter hole in the duct for the sensor probe and lug.1.
Affix foam gasket material to probe side of junction box.2.
Insert probe into duct.3.
Secure the junction box housing to outer surface of duct using self-tapping screws 4.
(not included).
Wire as shown (see Wiring section).5.
TA
TAR
TAR Model
TA Model
1.8"
(44.5 mm)
0.5"
(5 mm)
2.3"
(58 mm)
Bendable Tubing
4"
(102 mm)
4.2"
(107 mm)
1.8"
(44.5 mm) “ L”
0.5"
(5 mm)
2.3"
(58 mm)
Rigid Probe
4.2"
(107 mm)
Sensor Type
TA
Flexible
Probe Length
B = 100R platinum, RTD
C = 1k platinum, RTD
D = 10k, T2, Thermistor
H = 10k, T3, Thermistor
J = 10k, Dale, Thermistor
M = 20k, NTC
N = 1800 ohm, Thermistor
P = 10mV/C, Linitemp
R = 10k US, Thermistor
*M = 6' (1.8m)
H = 12' (3.6m)
J = 24' (7.3m)
Cal Certificate
0 = None
1 = 1 point Cal validation **
2 = 2 point Cal validation ***
* Available with sensor types J,N,P
** The 18”, 24”, 30”, 36”, and 48” Rigid probes are calibrated to 22.5°C only.
*** Not available for Rigid probes longer than 12”. Available for all Flexible probe lengths.
TAR
Rigid
Probe Length “L
E = 12” (0.3m)
F = 18” (0.5m)
G = 24” (0.6m)
N = 30” (0.8m)
K = 36” (0.9m)
P = 48” (1.2m)

Summary of content (2 pages)