Install Instructions

Z207931-0C Page 1 of 9 ©2020 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0920
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classied locations.
Read and understand the instructions before installing this product.
Turn o all power supplying equipment before working on it.
The installer is responsible for conformance to all applicable codes.
If this product is used in a manner not specied by the manufacturer, the protection
provided by the product may be impaired. No responsibility is assumed by the
manufacturer for any consequences arising out of the use of this material.
Installation Guide
Air Quality
Product Identication
Product Overview
The CW2 Series of air quality sensors for living space is a exible multi-sensor platform for use with BAS controllers
designed to accept 4 to 20mA, 0 to 5Vdc or 0 to 10Vdc outputs. CW2 Series sensors are available with three user
interface options: touchscreen, LCD with three buttons and blank. CO2 and temperature sensors are included with
all CW2 Series air quality sensors. Models with VOC sensors and relative humidity sensors are also available.
* Replaceable 1% with NIST certicate, 2% with NIST certicate and 2% elements available.
** VOC only availble with temperature transmitter option
*** For analog non-display, non-RH, models with RTD/thermistor order from CWE2 line.
CW2 Series
Wall Mounted Air Quality Sensors
Specications
OPERATING ENVIRONMENT
Input Power Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Analog Output Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V
Operating Temp. Range 0 to 50 °C (32 to 122 °F)
Operating Humidity Range 0 to 95% RH non-condensing
Housing Material High-impact ABS plastic
Terminal Block Torque 0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)
CO2 TRANSMITTER
Sensor Type Non-dispersive infrared (NDIR), diusion sampling
Output Range 0 to 2000/5000 ppm (selectable)
Accuracy ±30 ppm ±3% of measured value
Repeatability ±20 ppm ±1% of measured value
Response Time <60 seconds for 90% step change
VOC TRANSMITTER OPTION
Sensor Type Solid state
Output Range 0 to 100% AQI for VOC
Accuracy ±15% of measured value
Output Scale 0 to 1,000 ppb of total VOC (TVOC)
CW2Txxxx CW2Lxxxx CW2Xxxxx
CW2
User Interface Output RH Accuracy* Temperature VOC Sensor
T = Color touchscreen
L = 3-button LCD display
X = None***
A = Analog output 2 = 2%
X = None***
A = Transmitter
C = 1000 PT RTD
D = 10K T2 thermistor
H = 10K T3 thermistor
K = 10K curve G/11K shunt
M = 20K NTC thermistor
N = 1.8K TAC thermistor
V = NDIR CO/VOC**
= None