Product Overview
SPECIFICATIONS
Sensor Power N.O models: Induced from monitored current;
H800NC: 5 to 30 Vdc, permanently connected
Insulation Class 600 Vac RMS (UL), 300 Vac RMS (CE)
Frequency Range 50/60 Hz, On/O status for Variable Frequency Drive
(VFD) outputs at 12 to 115 Hz (a)
Temperature Range:
H800NC, H300, H900
H600
H800, H800HV
-15 to 60 °C (5 to 140 °F)
-15 to 40 °C (5 to 104 °F) (to 200 A);
-15 to 60 °C (5 to 140 °F) (to 150 A)
-40 to 50 °C (-40 to 122 °F) (to 200 A);
-40 to 75 °C (-40 to 167 °F) (to 100 A, and 0.25 A
status output)
Humidity Range 10 to 90% RH non-condensing
O State Leakage
(H800NC Only)
34 μA @ 5 Vdc, 200 μA @ 30 Vdc
On State Voltage Drop
(H800NC Only)
1.9 Vdc (max.) @ 0.1 A
Maximize Reliability
Minimize Installed Cost
HX00 SERIES
On/Off Status Current Switches
APPLICATIONS
Hawkeye x00 on/off current switches provide a cost-effective solution
for monitoring status on unit vents, exhaust fans, recirculation pumps,
and other fixed loads where belt loss is not a concern.
Veris has applied new technology to the H300, H600, and H800 models
to achieve impressive improvement in turn-on levels. The Hawkeye
H300 and H600 have the lowest turn-on current in the industry at a
mere 0.15 A!
H800
H300
H900
H600
Terminal Block Wire Size
H600, H800, H900
H300
24 to 14 AWG (0.2 to 2.1 mm
2
);
22 to 16 AWG (0.3 to 1.3 mm
2
)
Terminal Block Torque
H600, H800, H900
H300
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m);
7 in-lbs (0.8 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency approvals UL 508 open device listing; CE: EN61010-1, CAT III,
Pollution Degree 2, basic insulation
Note: Do not use the LED status indicators as evidence of applied voltage.
(a) VFD systems generate fields that can disrupt electrical devices. Ensure that these
fields are minimized and are not affecting the sensor.
• Electrical load status
• Direct-drive units, exhaust
fans, process motors, and other
fixed loads
• Lighting run times and status
• VFD output On/Off status
• Direct-Drive units, unit vents,
fan coil units, exhaust fans, and
other fixed loads
E150462
Reliable
More reliable for status than relays
across auxiliary contacts
Installation
flexibility
Removable mounting bracket
provides installation flexibility
Ideal for direct-
drive units
Ideal for direct-drive units, unit
vents, fan coil units, exhaust fans,
and other fixed loads
Flexibility
Bracket on H900 can be installed
in three different configurations
Low setpoint
Minimum trip point as low as
0.15 A (H600)…avoids the need for
multiple wraps of the conductor
through the sensor even on loads
as small as 1/5 HP
Quick installation
Split-core H300, H600 and H900
for fast retrofit installation