Product Overview

Sensor Power Induced from monitored conductor
Insulation Class 600 Vac RMS (UL), 300 Vac RMS (CE)
Frequency Range 50/60 Hz nominal
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Accuracy ±2% F.S. from 10% to 100% (range)
Response Time 2 sec.
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals
UL 508 open device listing; CE: EN61010-1, CAT III,
Pollution Degree 2, basic insulation
SENSED AMPS
Selected Range*
0 Vdc
0 A
5 Vdc
SENSOR OUTPUT
*Factory calibrated ranges selected
with the amperage range switch
H922
H822
H622-xx
H722 LC
Maximize Reliability
Minimize Installed Cost
TM
SPECIFICATIONS
EXAMPLE LINEAR OUTPUT
Scale software as shown
APPLICATIONS
Load trending
Motor control
Positive proof of flow
The Hawkeye 622-xx, 722, 822, and 922 provide accurate load
trending information with a proportional 0 to 5 Vdc output signal.
Slide-switches provide easy field selection of monitored amperage
range without jumpers (available on some models).
E150462
Self-powered
analog
Self-powered analog current
sensor simplifies installation
New
construction
Economical solid-core models
feature adjustable bracket for
easy alignment (H722xC)
No external
power required
No external power required for
sensor
Factory
calibrated
Factory calibrated ranges
for increased flexibility and
resolution
Retrofit
Self-gripping, split-core design for
fast retrofit installation…no need
to remove conductor (H622-xx,
H922)
No jumpers
No jumpers on unit…reduces
installation error
800.354.8556 
|
 +1 503.598.4564 
|
sales@veris.com
|
intl@veris.com
|
veris.com
HX22 SERIES