Install Instructions

Z201380-0V PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 03132
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
ENVIRONMENTAL SENSORS
INSTALLATION GUIDE
Digital RH and RH/T Transmitters
SPECIFICATIONS
Input Power: *
Voltage Models 12-30VDC/24VAC, 15mA max.
mA Model loop powered 12-30VDC only, 30mA max.
Output Power:
Voltage Models 3-wire, observe polarity
mA Model 2-wire, not polarity sensitive (clipped and capped)
Humidity:
HS Element Digitally proled thin-lm capacitive (32-bit mathematics)
U.S. Patent No. 5,844,138
Accuracy @ 25°C from 10-80% RH** ±1%, ±2%, ±3%, or ±5% (specify);
Multi-point calibration, NIST traceable
Temperature Eect, Duct Model +0.1% RH/°C above or below 25°C (typical)
Temperature Eect, Outdoor Model mA version: (0.0013x%RHx(T°C-25));
Volt version: (0.0015c%RHxT°C-25)) - (%RHx0.0008xabs(T°C-25))
Scaling 0-100%RH
Hysteresis 1.5% typical
Linearity Included in Accuracy spec.
Reset Rate*** 24 hours
Stability ±1% @ 20°C (68°F) annually, for two years
Temperature:
Optional Temperature Transmitter Output Digital, 4-20mA (clipped and capped) or
0-5V/0-10V output;
HD transmitter accuracy: ±0.5°C (±1.0°F) typical
Operating Environment:
Operating Humidity Range 0 to 100% RH noncondensing
Operating Temperature Range -40° to 50°C (-40° to 122°F)
Agency Approvals EMC EN 50081-1, EN 50082-1, EN 61000-4-4, EN 61000-4-5,
EN 61000-4-3, ENV 50204, EN 61000-4-6
* One side of transformer secondary is connected to signal common. Isolation transformer or
dedicated power supply may be required.
** Specied accuracy with 24 VDC supplied power with rising humidity.
*** Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
RTD Thermistors are not compenstated for internal heating of product.
To conform to EMC standards, shielded cabling and technical information is available from the
factory upon request or is available on our website: www.veris.com
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor
with proper surge protection (EN 61000-6-1:2007 specication requirements).
HD SerieS
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classied locations.
Read and understand the instructions before installing
this product.
Turn off all power supplying equipment before working on it.
The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
PRODUCT IDENTIFICATION
Available
T = Temp
X = No Temp
(Stop here)
US or EU Temp.
Sensor Type
Accuracy
NIST
S = Standard
C = CE
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k with 11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
Q = 1uA/˚C, Linitemp
R = 10k US, Thermistor
S = 10k 3A 221, Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
Output
M = 4-20mA
V = 0-5V/0-10VDC
1 = 1%
2 = 2%
3 = 3%
5 = 5%
HD
Sensor Type Range
Temp Cert
Blank = None
1 =1pt Cal
2 = 2pt Cal
OPTION
Humidity Transmitter Combination
Humidity RTD/Thermistor Combination
Blank = None
1 =1pt Cal
2 = 2pt Cal
A
= Transmitter
N = NIST
X = None
Temp Cert
OPTION
1 = -40° to 50°C
(-40° to 122°F)
2 = 0° to 50°C
(32° to 122°F)
INSTALLATION
1. Choose a location on the return air duct.
2. Drill a 7/8” diameter hole in the duct for the sensor probe.
3. Mount the junction box housing to the duct using self-tapping screws (included).
4. Insert the probe through the black swage tting into the duct. Tighten the swage
tting.
5. Wire the probe (see the Wiring section). Leave wires at factory length to allow
for a service loop (to remove the sensor from junction box for service without
disturbing the conduit).
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.

Summary of content (3 pages)