Install Instructions

Z205847-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
EnvironmEntal SEnSorS
inStallation GUiDE
Economy Wall Mount Humidity Sensor
HEW SEriES HEW SEriES
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
Read and understand the instructions before installing
this product.
Turn off all power supplying equipment before working on it.
The installer is responsible for conformance to all applicable codes.
Product IdentIfIcatIon
quIck Install
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Mount the backplate on the wall in an appropriate location. Place so that the
“Install This End Up” statement on the board is in the upper right corner.
2. Wire the unit as shown (see Wiring section).
3. Attach the front plate.
Output Temp.
Sensor Type
Accuracy
M = 4-20mA
V = 0-5V/0-10V
A = Temp Transmitter
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k with 11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
R = 10k US, Thermistor
S = 10k 3A 221 Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor
HEW
T = Temp
X = No Temp
(Stop here)
Installer’s Specifications
Input Power:
Input Power, Voltage Version 12-24 VDC or 24 VAC
Input Power, mA Version 12-24 VDC
AC Voltage Tolerance ±10%
AC Frequency 50-60 Hz
Max. Inrush Current After 1 msec (mA version) 25 mA
Output Power:
mA Output 4-20 mA, 2-wire, polarity insensitive
mA Max. Loop Resistance 500 Ω at 24 VDC input voltage; 250 Ω at 12 VDC input voltage
Voltage Output 0-5 V or 0-10 V (jumper selectable)
Voltage Min. Load Resistance 5 kΩ
Voltage Min. Sinking Current 0.2 mA
Humidity:
HS Element Digitally proled thin-lm capacitive, non-removable
Accuracy ±2%, 3% or 5% (10-90% RH, 20° to 30°C (68° to 86°F))
Temperature Eect (Outside 20° to 30°C) ≤0.1% RH per °C
Response Time (to 90% change at 20°C) 110 sec
Annual Drift ≤1%
Output Scaling 0-100% RH
Temperature:
Active Output Accuracy ±0.5°C
Active Output Temperature Scaling 10° to 35°C (50° to 95°F)
Resistive Temperature Accuracy see thermistor table
Self-Heating Error (Resistive Temperature Only) ≤±0.5°C at 20° to 30°C (68° to 86°F);
≤±0.75°C outside of 20° to 30°C (68° to 86°F)
Operating Environment:
Operating Temperature 0° to 50°C (32° to 122°F)
Operating Humidity 0-100% RH (non-condensing) (Unit will recover from saturation)
Housing:
Material ABS plastic with UL V-0, 5VB Flame Class
Mounting Holes US and European junction box
EMC Conformance: EN61000-6-3:2007+A1:2011 Class B, EN61326-1:2006 Class B; EN61000-6-
1:2007
1-year limited warranty.
S
= Standard
Temp Cert
Blank = None
1 = 1 pt cal
2 = 2 pt cal
RoHS
Compliant
2 = 2%
3 = 3%
5 = 5%