Product Overview
HEW
INPUT POWER
Voltage Model Class 2; 12 to 24 Vdc or 24 Vac
mA Model Class 2; 12 to 24 Vdc
AC Voltage Tolerance ±10%
AC Frequency 50/60 Hz
Max. Inrush Current after 1 msec (mA
version)
25 mA
OUTPUT
mA Output 4 to 20mA, 2-wire, not polarity sensitive
mA Max. Loop Resistance
500 Ω at 24 Vdc input voltage; 250 Ω at
12 Vdc input voltage
Voltage Output 0 to 5 V or 0 to 10 V (jumper selectable)
Voltage Min. Load Resistance 5 kΩ
Voltage Min. Sinking Current 0.2 mA
HUMIDITY
RH Element
Digitally proled thin-lm capacitive,
non-removable
Accuracy ±2%, 3%, or 5% (10 to 90% RH, 20 to 30 °C)
Temperature Eect (Outside 20° to 30°C) ≤0.1% RH per °C
Response Time (to 90% change at 20°C) 110 sec
Annual Drift ≤1%
Output Scaling 0 to 100% RH
TEMPERATURE OPTION
Active Output Accuracy ±0.5 °C (±.9 °F)
Active Output Temp Scaling 10 to 35 °C (50 to 95 °F)
Self-Heating Error
(Resistive temperature only)
≤±0.5 °C at 20 to 30 °C (68 to 86 °F);
≤±0.75 °C outside of 20 to 30 °C (68 to 86 °F)
OPERATING ENVIRONMENT
Operating Temperature 0 to 50 °C (32 to 122 °F)
Operating Humidity
0 to 100% RH non-condensing
(Unit will recover from saturation)
HOUSING
Material ABS plastic with UL V-0 5VB Flame Class
Mounting Holes US and European junction box
WARRANTY
Limited Warranty 1 year
2%, 3%, AND 5% ACCURACIES
FEATURES
• Monitor humidity and temperature with a single device...reduces
installation costs
• Semiconductor temperature transmitter, or popular
thermistor/RTD sensors available
• Housing is low-prole...perfect for schools and museums
DESCRIPTION
HEW Standard Series wall mount humidity transmitters oer high
performance in an easy to install housing at an aordable price. The thin-
lm capacitive sensor element provides high accuracy and performance,
great long-term stability, and full recovery from saturation. Temperature
sensing options are also available.
The wall housing was created using sophisticated thermal analysis
techniques for optimum airow. It is ideal for schools and other
applications requiring exceptional durability and a discrete appearance. All
Standard models come with a standard one-year warranty.
APPLICATIONS
• HVAC economizer control
• Managing energy systems
• Facilitating ASHRAE standards for environmental control
IDEAL FOR
BID SPEC
SPECIFICATIONS
EMC Conformance: Low Voltage Directive 2006/95/EC and EMC Directive 2004/108/EC.
Humidity Monitoring |
For more information on how Veris products can help optimize your systems:
Call: Toll-free 800.354.8556 | Intl. +1 503. 598.4564 Email: sales@veris.com | intl@veris.com
TM
Standard Wall Humidity Sensors
HEW Series
HQ0001720.F 0116