Product Overview

GENERAL
Input Power Class 2; 15 to 30 Vdc, 24 Vac nom. 50/60 Hz*
Max. Current Draw DC: 125 mA; AC: 280 mA
Output 3-wire transmitter; user selectable 4 to 20 mA
(clipped & capped)/0-5 V/0-10 V*
Surge Damping Electronic; 1 or 5 second averaging
Test Mode Overrides output to full-scale (20 mA, 5 V, 10 V)
Zero Adjust Pushbutton auto-zero & digital input (2-pos
terminal block)
Status Indication Dual-color LED:
Green = Normal, Green Blinking = Low > High
Red = Overrange, Red Blinking = Overpressure
Green/Red Blinking = Underpressure
Zero Offset
(Bidirectional and Port
Swap modes only)
0.5%
Housing Material White powder-coated aluminum
NEMA 4, IP65
Fittings 1/8” NPT female thread, 17 to 4 PH stainless steel
PRESSURE RANGES (SELECTABLE)
0 to 50 psig (Gauge) 0 to 5/10/25/50 psid (Differential)
0 to 100 psig (Gauge) 0 to 10/20/50/100 psid (Differential)
0 to 250 psig (Gauge) 0 to 25/50/125/250 psid (Differential)
SENSOR
Accuracy @ 25 °C** Ranges A and B: ±1% F.S. typical***;
Range C: ±1.5% F.S. typical***;
Range D: ±2% F.S. typical***
*VFD systems and system wiring generate fields that can disrupt electrical devices. Ensure
that these fields are minimized and are not affecting the sensor or sensor wiring.
**Accuracy combines linearity, hysteresis, and repeatability.
*** FS is defined as full span of selected range in bi-directional mode.
EMC Conformance - Low voltage directive 2014/35/EU; EMC directive 2014/30/EU.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power
adaptor with proper surge protection (EN 61000-6-1 specification requirements).
The PW Series wet pressure transducers incorporate microprocessor
profiled sensors for exceptional accuracy and reliability. Easy to use
and designed to provide exceptional installation savings, the PW Series
is ideal for measuring pressure across pumps, filters, heat exchangers,
compressors, and other non-corrosive wet media applications.
The DIP switch selectable port swap feature eliminates costly
replumbing when the high and low ports are improperly plumbed,
allowing the DIP switch position to be changed from normal to swap.
The optional pre-assembled bypass valve is designed for easy
maintenance and one-step installation.
APPLICATIONS
Monitoring and controlling
pump differential pressure
Chiller/boiler differential
pressure drop
CW/HW system differential
pressure
Flexible
The DIP switch selectable output
switch for normal (4 to 20 mA) or
reverse (20 to 4 mA) operation
provides application flexibility
Switch-selectable
Switch-selectable pressure
ranges
fewer models to order
and stock
Rugged
Rugged, die-cast enclosure
provides NEMA 4 sealing
Zero calibration
Pushbutton and remote zero
adjustment
maintain accuracy and
reduce callbacks with automatic
zero calibration
High stability
DIP switch controlled electronic
surge dampening
SPECIFICATIONS
Long Term Stability ±0.25% per year
Media Compatibility Media compatible with 17 to 4 PH stainless steel
Proof Pressure 2x max. F.S. range***
Burst Pressure 5x max. F.S. range***
Temperature
Compensated Range
0 to 50 °C (32 to 122 °F);
TC Zero <±1.5% of product F.S.*** per sensor ;
TC Span<±1.5% of product F.S.*** per sensor, (2
sensors per unit)
Media Temp. Limits -20 to 85 °C (-4 to 185 °F);
0 to 90% RH non-condensing
Operating Environment -10 to 50 °C (14 to 122 °F); 10 to 90% RH
non-condensing
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
PWxxxS
PWxxxBP
800.354.8556 
|
 +1 503.598.4564 
|
sales@veris.com
|
intl@veris.com
|
veris.com
PW SERIES
DIP Switch Selectable Port Swap Feature
Pressure Monitoring | Wet Media Differential Pressure Transducers
HQ0001831.M 0321

Summary of content (2 pages)