Install Instructions
Z203571-0K Page 1 of 2 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0119
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
•
Read and understand the instructions before installing this product.
• Turn o all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
If this product is used in a manner not specied by the manufacturer, the protection
provided by the product may be impaired. No responsibility is assumed by the
manufacturer for any consequences arising out of the use of this material.
Installation Guide
Temperature
Product Identication
Product Overview
The TJ Series temperature sensor is designed for VAV systems. The cable is plenum rated, and the probe is stainless
steel for durability. The TJ is warranted for a period of ve years.
TJ Series
VAV Discharge Temperature Sensor
Specications
Wiring 22 AWG; 2-wire RTD/Thermistor
Probe Stainless steel
Operating Temperature Probe: -25° to 105 °C (-13 to 221 °F)
Wiring side: Up to 75 °C (167 °F)
WARRANTY
Limited Warranty 5 years
Sensor Type OptionProbe Length
B = 4" (102 mm)
D = 8" (204 mm)
TJ
0 = Standard 5 ft.
cable, no QDs
1 = 1/4" Female
Quick Discon-
nects (QD)
2 = 1/4” QDs with
8 ft. lead wires
3 = 10 ft. cable,
no QDs
= Resistive
Cal Certificate
0 = None
2 = 3-Point NIST calibration
R
Output
B = 100R platinum, RTD
C = 1k platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
H = 10k T3, Thermistor
I = 1k Balco (Nickel-Iron) RTD
J = 10k Dale, Thermistor
K = 10k w/11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm, Thermistor
T = 100k, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Notes:
Increased cable length aects the readings of lower resistance RTDs (100R platinum RTD).
Room temperature oset documented on each unit.
TJ