Direct Vent Top Vent Model BHDT36 Installation Instructions & Homeowner's Manual WARNING! IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE,PERSONAL INJURY OR LOSS OF LIFE. FOR YOUR SAFETY FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS: DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE. • • • • Do not try to light any appliance.
TABLE OF CONTENTS PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE. Thank you and congratulations on your purchase. IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty. Installation Instructions ...........................................................................................................................................
INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT: PLEASE REVIEW THE FOLLOWING CAREFULLY This gas appliance should be installed by a qualified installer in accordance with local building codes and with current CAN / CGA-B149 (. 1 or .2) Installation codes for Gas Burning Appliances and Equipment. or for U.S.A Installations follow local codes and/ or the current National Fuel Gas Code. ANSI Z223.1. Remove any plastic from trim parts before turning the fireplace ON.
FIREPLACE DIMENSIONS N ROD ROH L M Framing Dimensions ROW E H G F C B I J K Fig.
FRAMING AND FINISHING MANTELS Depending on the width of the mantel it may be installed higher or lower from the top of the louvre opening. See drawing and chart below for proper installation height of your combustible mantel piece. Non-combustible mantels may be installed at any height above the appliance opening. 1. 2. When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant to prevent discolouration. 3. ,, ,, ,, 4. V 5.
The installation of your Majestic Fireplace must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1 latest edition, or CAN 1 B1-149.1 and .2 Installation Code. (EXCEPTION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5 inches W.C. for Natural Gas and 10 inches W.C. for LP gas.) HEARTH A hearth is not mandatory but it is recommended for aesthetic purposes.
GAS LINE INSTALLATION REMOTE SWITCH INSTALLATION 1. Thread wire through the electrical knockout located on either side of fireplace.. Do not cut wire or insulation on metal edges. Ensure that wire is protected. Run the other end to a conveniently located wall receptacle box. 2. Attach wire to switch and install switch into receptacle box. Attach cover plate to switch. 3. Connect wiring to gas valve. (Fig. 8/9) When purging gas line the front glass must be removed.
GENERAL VENTING Your fireplace is approved to be vented either through the side wall, or vertical through the roof. There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front of the termination hood. - Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system.
Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors. Inside Corner A V Recessed Location Outside Corner A= Combustible 6"(152mm) Noncombustible 2"(50mm) D B= Combustible 6"(152mm) Noncombustible 2"(50mm) V C C E V B Balcony with perpendicular side wall Balcony with no side wall G C = Maximum depth of 48" (1219mm) for recessed location.
GENERAL INFORMATION ON ASSEMBLING THE VENT PIPES WITH CRIMPED ENDS For some installations, it may be desireable to have some amount of the horizontal vent run immediately after the fireplace. A vertical rise must be used but can be located anywhere in the vent system, to meet the perimeters identified in the venting graph. Before joining elbows and pipes apply a bead of high temperature sealant to crimped end of 4" and 7" elbow or pipe. (Fig.
If a 90 degree elbow is used in the horizontal vent run (level height maintained) the maximum horizontal vent length is reduced by 36 inches. Fig. 15. This does not apply if the 90 degree elbows are used to increase or redirect a vertical rise. HOW TO USE THE VENT GRAPH 1. Determine the height of the centre of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 17), locate the point it intersects with the slanted graph line. 2.
VERTICAL SIDEWALL INSTALLATION #8 SCREWS(2) Maximum Length 12" (294mm) ADJUSTABLE ZERO CLEARANCE SLEEVE #8 SCREWS(2) STEP 1 #8 SCREWS(2) Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (For combustible walls first frame in opening). ADJUSTABLE ZERO CLEARANCE SLEEVE FIRESTOP Fig.
STEP 5 (Fig. 23) Use the appropriate length of pipe section – telescopic or fixed – and install. The 20" (508mm) section of pipe which goes through the wall is packaged with the 7DVSK kit, and can be cut to suit if necessary. Sealing vent pipe and firestop gaps with hitemperature sealant will restrict cold air being drawn in around fireplace. STEP 7 , , , , , , Fig. 24 Support the horizontal pipes every 36 inches (914mm) with metal pipe straps.
BELOW GRADE INSTALLATIONS When it is not possible to meet the required vent terminal clearances of 12 inches (305mm) above grade level a model #7DVSKS vent kit is required. It allows installation depth of down to 7 inches (178mm) below grade level. The 7 inches is measured from the centre of the horizontal vent pipe as it penetrates through the wall.
VERTICAL THRU THE ROOF INSTALLATION 1. Locate your fireplace. 2. Plumb to centre of the (4") collar from ceiling above and mark position. 3. Cut opening equal to 9-3/8" x 9-3/8" (240 mm x 240 mm). 4. Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1 inch clearance to the vent pipe, i.e., the hole must be a minimum of 9-3/8" x 9-3/8" (240 mm x 240 mm). 5. Place firestop(s) 7DVFS into position and secure. (Fig. 32) 6. Install roof support (Fig.
CRIMPED ENDS VENTING COMPONENTS Starter Kit -Model 7DVSK - Sidewall Venting Starter Kit - Model 7DVSKV - Vertical Venting for 7DVSKV-A order 1/12 to 6/12 roof pitch for 7DVSKV-B order 7/12 to 12/12 roof pitch for 7DVSKV-F order flat roof Starter Kit - Model 7DVSKS -Snorkel Kit for Below Grade Installation 45º elbow kit 7DVT45 for Vertical Installation Offsets 90º transition elbow kit 7DVRT90 for Vertical Sidewall Applications or thru-the-roof.
GENERAL INFORMATION ON ASSEMBLING THE TWIST LOCK VENT PIPES When using CFM Majestic twist lock pipe it is not necessary to use silicone to seal the twist lock joints. The only areas that need silicone are the collars on the fireplace, the telescoping pipe (if used) and the horizontal termination connection (when necessary). VERTICAL SIDEWALL APPLICATIONS Vent Starter Kit 7TDVSK must be used in Vertical Sidewall installations.
The maximum number of 90 degree elbows per side wall installation is three (3). The maximum number of 45 degree elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run. The maximum horizontal vent length is 36" (914mm) when 90º elbow is installed directly onto fireplace. 3 FT (92cm) Fig. 36 Fig.
HOW TO USE THE VENT GRAPH VERTICAL SIDEWALL INSTALLATION 1. Determine the height of the centre of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 39), locate the point it intersects with the slanted graph line. 2. From the point of this intersection, draw a vertical line to the bottom of the graph. 3. Select the indicated dimension, and position the fireplace in accordance with same.
STEP 5 #8 SCREWS(2) Maximum Length 12" (294mm) ADJUSTABLE ZERO CLEARANCE SLEEVE #8 SCREWS(2) (Fig. 45) Use the appropriate length of pipe section – telescopic or fixed – and install. The 20" (508mm) section of pipe which goes through the wall is packaged with the 7TDVSK kit, and can be cut to suit if necessary. #8 SCREWS(2) ADJUSTABLE ZERO CLEARANCE SLEEVE FIRESTOP Fig. 42 Sealing vent pipe and firestop gaps with hitemperature sealant will restrict cold air being drawn in around fireplace.
STEP 7 , , , , , , Fig. 46 Support the horizontal pipes every 36 inches (914mm) with metal pipe straps. Make sure that the horizontal vent pipe is installed on a level horizontal plane. STEP 8 Recheck the fireplace to make sure that it is levelled, properly positioned, and nailed or screwed to the floor. If applied, the fireplaces adjustable frame drywall strips (nailing flanges) should be fastened. See "Framing & Finishing.
MAX. 8 FEET FOUNDATION RECESS SNORKEL WATERTIGHT SEAL AROUND PIPE 2438mm 45° WALL SCREWS 40 FEET (12.2m) MAX. 8 FEET 2438mm SHEET METAL SCREWS TYPICAL 7DVCS APPLICATION Fig. 51 45° Fig. 48 If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first and then secure to snorkel with self drilling #8 x 1/2 sheet metal screws. It will be necessary to extend vent pipes out as far protruding wall face (Fig. 48).
VERTICAL THRU THE ROOF INSTALLATION 1. Locate your fireplace. 2. Plumb to centre of the (4") collar from ceiling above and mark position. 3. Cut opening equal to 9-3/8" x 9-3/8" (240 mm x 240 mm). 4. Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1 inch clearance to the vent pipe, i.e., the hole must be a minimum of 9-3/8" x 9-3/8" (240 mm x 240 mm). 5. Place firestop(s) 7DVFS into position and secure. (Fig. 54) 6. Install roof support (Fig.
TWIST LOCK VENTING COMPONENTS Starter Kit -Model 7TDVSK - Sidewall Venting Starter Kit - Model 7TDVSKV - Vertical Venting for 7TDVSKV-A order 1/12 to 6/12 roof pitch for 7TDVSKV-B order 7/12 to 12/12 roof pitch for 7TDVSKV-F order flat roof Starter Kit - Model 7TDVSKS -Snorkel Kit for Below Grade Installation 45º elbow kit 7DVT45 for Vertical Installation Offsets 90º transition elbow kit 7TDVRT90 for Vertical Sidewall Applications or thru-the-roof.
OPERATING INSTRUCTIONS GENERAL GLASS INFORMATION GLASS FRAME FIREPLACE FRONT Only glass approved for use in Majestic products may be used for replacement. 1 . The use of subsitute glass will void all product warranties. 2. Care must be taken to avoid breakage of the glass. 3. Under no circumstances should this appliance be operated without the front glass or with a broken glass. Replacement of the glass (with gasket) as supplied by the manufacturer should be done by a licenced qualified service person.
INSTALLATION OF LOGS LAVA ROCK 1 . Remove front glass. (See "Glass Removal" Section) 2. Remove logs from the packaging. The lava rock provided with this fireplace must be placed on the firebox base on either side of the burner assembly. Under no circumstances should this lava rock be placed on any part of the burner assembly. As with all plastics — these are not toys and should be kept away from children and infants. 3.
FLAME CHARACTERISTICS MAINTENANCE 1. It is important to keep the burner and the burner compartment clean. This must be done periodically, at least once per season. 2. Clean the brass trim using a soft clean cloth, slightly dampened withlemon oil and buff with a soft clean cloth. Do NOT use brass polish or household cleaners as these products will damage the brass trim. Lemon oil can be obtaned at supermarkets or hardware stores. 3. The optional FK24 fan does require periodic cleaning.
LIGHTING AND OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. B. This fireplace has a pilot which must be lit manually. When lighting the pilot follow these instructions exactly. BEFORE LIGHTING smell all around the fireplace area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
TROUBLE SHOOTING THE GAS CONTROL SYSTEM HONEYWELL MILLIVOLT VALVE START CHECK • GAS SUPPLY ON NO YES PILOT LIGHTS WITH PIEZO IGNITOR NO YES PILOT STAYS LIT YES • LOCKOUT HAS ENGAGED. WAIT 60 SECONDS AND TRY AGAIN. • FOR SPARK AT ELECTRODE WHILE DEPRESSING PIEZO — 1/8" GAP TO PILOT HOOD NEEDED. • ALL WIRING CONNECTIONS • REPLACE PIEZO IGNITOR NO • FOR AIR IN THE LINES • THERMOPILE NEEDS A MINIMUM 325mV. ADJUST PILOT FLAME HEIGHT. • ALL WIRING CONNECTIONS.
TROUBLE SHOOTING THE GAS CONTROL SYSTEM SIT 820 NOVA MILLIVOLT VALVE GLASS DOOR TO BE REMOVED BEFORE SERVICE WORK CHECK NO GAS SUPPLY ON • SHUTOFF VALVE OPEN • CONFIRM GAS HOOK-UP NO ▼ ▼ ▼ START LIGHT PILOT WITH PIEZO IGNITION YES • • • • ELECTRODE GAP MIN.
REPLACEMENT PARTS LIST DESCRIPTION 1. 1a. 1b. 1c. 1d. 2. 3. 4a. 4b. 5a. 5b. 6a. 6b. 7a. 7b. 8a. 8b. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19a. 19b. 20a. 20b. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. Log Set Complete Log Front Log Rear Log Top Left Log Top Right Lava Rock (Package) Burner Tube Assembly Orifice Burner (Nat) Orifice Burner (Prop) Orifice Pilot SIT (Nat) Orifice Pilot SIT (Prop) Orifice Pilot PSE (Nat.) Orifice Pilot PSE IProp.
REPLACEMENT PARTS 7 a/b 31 30 2 31 30 19 a/b 32 24 29 9 16 4 a/b 33 12 25 PI PILOT ADJ ON O H 13 15 26 L I LO T OFF 20 a/b 18 11 21 27 17 23 8 a/b 5 a/b 36 22 34 6 a/b 28 3 10 15 14 #1 - COMPLETE LOG SET 1d 1c 1b 1a - 32 -
OPTIONAL FAN KIT - FK24 WIRING INSTRUCTIONS Fan Specifications: 120 Volt 60 HZ .75 Amp. Hard (DIrect) Wire Hook-Up This fan does not need regular maintenance, however periodic cleaning is required. Check the area under the control door and in front of the fan and wipe or vacuum at least once a month during the operating season. First connect ground wire to ground stud located on the base of either box. Black wire from supply should connect to the variable speed switch.
6. Hang Bay Window Frame assembly over existing glass frame. TOP TRIM SUPPORT Do not remove existing glass frame 7. Re-install top louvre assembly. MAIN FRAME Remove all plastic from brass trims BOTTOM TRIM SUPPORT 8. Open the Bottom Bay Louvre door and screw two (2) self tapping screws (as per step 1 above) to the bottom of the unit where the hinges were 9. Bottom brass trim is removable when unit is installed with marble or tile surround which cover the fireplace bottom.