Specifications

DFS Series Vent Free Fireplace
71D0532 9





     



     



The clearance from the
inside of the appliance to any combustible adjacent wall
should no be less than 9". Figure 4
The ceiling must be at least 42" from
the top of the rebox opening. Figure 4
  The appliance may be placed
against a combustible back wall.
This replace may be installed directly
onto a combustible oor or raised on a platform of appro-
priate height. Do not install the replace directly onto any
soft ooring material such as carpeting, vinyl tile or other
combustible material other than wood ooring, unless there
is a sheet metal panel (.030” minimum thickness) or at
wood, plywood or particle board panel (1/2” minimum thick-
ness) extending the full width and depth of the enclosure.
Be sure rebox rests on a solid continuous oor or platform
with appropriate framing for support.
  The canopy supplied with the unit
must be installed. If a combustible mantel is installed. It
must meet the clearance requirements shown in Figures
5 & 6.
9"
Minimum
9"
Minimum
42" Minimum
FP2441
sidewall clg clear


FP2441
Combustible mate-
rial can contact top
of replace
Noncombustible material
only if needed to cover
optional radiant top
panel above canopy
FP2442


12”
8”
8”
14”
FP2443
mantel clear wide hood


Refer to Page 35)
FP2444
45°
1”
256O
3”
5”
6”
56O
56O
56O
FP2692
mantel leg clearance
6”
756O
756O
9”
Finish Wall
Combustible Material
Area



 The Vermont Castings Group Barrington Cabinet
Mantel Model series BWC300, BWC400 and BWC500 are
specially designed to comply with all mantel temperature
requirements. Any custom-built mantel must comply with all
clearance requirements shown in this instruction manual.