3.6 Faults
The UPS displays fault codes when it detects a problem and automatically shuts-off output power.
FAULT
CODE
DESCRIPTION SUGGESTED TROUBLESHOOTING
E01 Output short circuit.
Turn-off the UPS, disconnect all loads, and restart the UPS.
• If the fault is still active, contact Vertiv technical support for a replacement.
• If the fault is no longer active, plug in equipment one at a time to locate the device
with the short circuit.
E02
Output overload exceeded warning
time, and output is shut off.
Turn-off the UPS, disconnect all loads, and restart the UPS. Plug in equipment one at a time and
make sure not to exceed the UPS rating for load capacity.
E03 Un-used. Un-used.
E04
Internal inverter circuitry failure
during start-up self-test.
Turn-off the UPS and call Vertiv technical support for a replacement unit.
E05 Battery-charge failure. Turn-off the UPS and call Vertiv technical support for a replacement unit.
E06 Internal battery is dead or damaged.
Charge the UPS for at least 12 hours or replace the battery, see Battery Replacement on
page18.
Table 3.5 Fault Codes and Actions
3.7 Normal Start-up
• With the UPS connected to AC input, press-and-hold the power button for 1 second.
A long tone and 2 short beeps sound while the UPS is in battery self-test mode for a few
seconds. After a successful self-test, the outlets are on.
3.8 Normal Shut-down
1. Press-and-hold the power button for 1 second.
The outlets are turned off.
2. Disconnect AC-input power.
3. Remove the battery cover and disconnect the battery connector.
3.9 Full Shut-down
1. Press-and-hold the power button for 1 second.
The outlets are turned off.
2. Disconnect AC-input power.
3. Remove the battery cover and disconnect the battery connector.
The unit is fully shut down.