Use and Care Manual
Table Of Contents
X1.GW531B.TY.F01M.Manufacturer Instruction Manual. 10/13
using please winding two or three laps on the sensor)
*Cool. I
rating
0.3A
0~35.0A
Phase
monitor
On_boar
d
IO_input;
On_board;
Forbid;
When [Phase monitor] is set “IO_input” and [DI3 input
opt] is set “Phase switch”.the function of switch DI3 is
phase protection
DI1 input opt
Cool
overload
Cool overload;
Anti-freezing
Selection of switch DI1 input function
DI6 input opt
Comp
overload
Comp
overload;
Cool W.flow
Comp overload: DI6 input for Comp overload detection
Cool W.flow: DI9 input for cool water flow detection
Temp.high
AL
Pump
keep
Pump stop ~
Pump keep
Pump stop: stop the cold pump in case of Temp.high
fault;
Pump keep: do not stop the cold pump in case of
Temp.high fault.
DI3 input opt
Cold
overload
Cold
overload~
Phase switch
Selection of switch DI3 input function
Temp.
Setting
Load offset
1.0℃
0~10.0℃
Temperature deviation of load the compressor, invisible
when parameter [Temp unit] is Fahrenheit.
Load offset
1.8℉
0~18.0℉
Temperature deviation of load the compressor, invisible
when parameter [Temp unit] is Celsius.
Unload
offset
1.0℃
0~10.0℃
Temperature deviation of unload the compressor,
invisible when parameter [Temp unit] is Fahrenheit.
Unload
offset
1.8℉
0~18.0℉
Temperature deviation of unload the compressor,
invisible when parameter [Temp unit] is Celsius.
T.setpoint
max
30.0℃
-38.0~99.9℃
Top limit of set temperature, invisible when parameter
[Temp unit] is Fahrenheit.
T.setpoint
max
86.0℉
-36.4~211.8℉
Top limit of set temperature, invisible when parameter
[Temp unit] is Celsius.
T.setpoint
min
5.0℃
-38.0~99.9℃
Bottom limit of set temperature, invisible when
parameter [Temp unit] is Fahrenheit.
T.setpoint
min
41.0℉
-36.4~211.8℉
Bottom limit of set temperature, invisible when
parameter [Temp unit] is Celsius.
T.bias
0.0℃
-9.9~9.9℃
Compensation for the liquid temperature, invisible when
parameter [Temp unit] is Fahrenheit.
T.bias
0.0℉
-17.8~17.8℉
Compensation for the liquid temperature, invisible when
parameter [Temp unit] is Celsius.
T.low protect
4.0℃
-40.0~99.9℃
Fault of “Temp.low AL” warning will be reported when
liquid temperature is lower than this value. Invisible
when parameter [Temp unit] is Fahrenheit.
T.low protect
39.2℉
-40.0~211.8℉
Fault of “Temp.low AL” warning will be reported when
liquid temperature is lower than this value. Invisible
when parameter [Temp unit] is Celsius.
T.high warn
50.0℃
0~99.9℃
Fault of “Temp.high warn” warning will be reported when
liquid temperature is higher than this value. Invisible
when parameter [Temp unit] is Fahrenheit.
T.high warn
122.0℉
32.0~211.8℉
Fault of “Temp.high warn” warning will be reported when
liquid temperature is higher than this value. Invisible
when parameter [Temp unit] is Celsius.
T.high alarm
60.0℃
0~99.9℃
Fault of “Temp.high AL” warning will be reported when
liquid temperature is higher than this value. And
meanwhile, the compressor will stop and then, the cool
pump. Invisible when parameter [Temp unit] is
Fahrenheit.
T.high alarm
140.0℉
32.0~211.8℉
Fault of “Temp.high AL” warning will be reported when
liquid temperature is higher than this value. And
meanwhile, the compressor will stop and then, the cool
pump. Invisible when parameter [Temp unit] is Celsius.
T.high reset
5.0℃
0~99.9℃
If liquid temperature<[T.high alarm]–[T.high reset],
manual reset of “Temp.high AL” fault will be allowed;
If liquid temperature<[T.high warn]–[T.high rese], the