Table of contents: page 1. Boiler use and advantages....................................................................................................................................3 2. Boiler VIADRUS G 300 technical data ............................................................................................................4 3. Description..........................................................................................................................................................5 3.1.
Dear customer we thank you that you decided to purchase VIADRUS G 300 boiler thus showing your confidence in company of ŽDB GROUP a.s., VIADRUS Heating technique plant. For you to get used to operating your new product correctly from the start please read carefully this manual instructing you how to use the product (first of all chapter No.7 - Boiler operation by user). Please follow the information stated in further text and also the Regulation No.91/93 Coll..
2. Boiler VIADRUS G 300 technical data Table No.1 Boiler thermo-technical parameters fuel efficiency : natural gas 33,99 MJ/kg Boiler size - number of ks 5 6 sections kW 103 126 Rated thermal output kW 113,2 138,5 Rated thermal input % Efficiency Fuels consumption natural gas m3/h 11,5 14,1 furnace oil extra light (TOEL) kg/h l 56,4 65,4 Boiler water volume Max. working water overpressure bar Max. operating temperature of °C heating water Combustion gas technical data Necessary draught mbar Max.
3. Description 3.1. Boiler construction The boiler body (Fig. No.1) consists of sections assembled by means of forced-on insertions and is secured by anchor bolts. Boiler has a three-draught construction and the sections create the combustion space and the convection part, inside then the boiler water space. The tightness of boiler gas combustion space is guaranteed by boiler cement applied to sections seating faces and to circumference of individual section joints.
Legend: F1 fuse 6,3 A S1 Main switch H1 Boiler under voltage signalling Z1 Suppression component BT1 Safety thermostat PS1 Water pressure manostat H2 Safety thermostat signalling K1 Eternal operation relay 6 BT2 Service thermostat X10 Burner connector H3 Burner defect signalling H4 Burner 2nd stage working signalling MPH1 Service hours gauge for 1st burner stage MPH2 Service hours gauge for 2nd burner stage BT3 Thermostat for 2nd burner stage X20 Burner connector COVER OF ELEKTROPANEL NOTE: Water pressu
Fig. No.3/1 Electro-panel wiring diagram 7 Cover of elektropanel Z1 Suppression component NOTE: Water pressure manostat (PS1) only in design for MORA company, in case it is used reconnect the conductor BT1:14 from terminal X1:8 to X1:9. – conductor nr.18. The outside control relay 24AVC(K1) only in design for SLANT/FIN firm; in case it isn’t used reconnect the conductor X10: T1 from terminal X1:12 to X1:13.
COVER Fig. No.
RJ protected input boiler circulation 1 NPE 50 Hz 230 V/16 A pump boiler main switch Boiler bypass pump failure 9 boiler burner Note 1) bypass pump controlled by a thermostat master control BOILER REGULATION Fig. No.
4. Positioning and installation 4.1. Boiler standing in boiler room L of boiler + min. 500 The boiler is designed for positioning in closed areas with aggressiveness degree between a little up to moderately aggressive and in terms of electrotechnic regulations in a common environment (ČSN 33 2000 – 7 – 701:1997). It agrees with the use in rooms separated from housing room itself (Declaration 91/93 Coll.., ČSN 07 0703:1986 Gas boilers).
Tab. No. 4 Flammability degrees of building materials and products Flammability degree of building materials and products A – fireproof B –flammable with difficulties C1 – hardly flammable C2 – mediumly flammable C3 – easily flammable The building materials and products ranged in flammability degree ( selection of ČSN 73 0823: 1984) Granite, sandstone, concretes, bricks, ceramic tiles, mortars, fire protection plasters ,….
The connection must carried out only if approved by a chimney organization wand must meet all provisions of these standards. The chimney must be resistant to combustion gases condensate, otherwise it might be seriously damaged. f ) with regard to fire regulations ČSN 06 1008 : 1997 Fire safety of heat installations . ČSN 73 0823 : 1984 Fire technical substances characteristics. Flammability degrees of building materials. 5. Order, delivery and assembly 5.1.
f) connection to the electricity network 230V/380V 50 Hz/TN-S g) connection to the chimney (the necessary chimney draught is 0,5 mbar). h) max. overpressure in combustion chamber is 2 mbar. The probe positioned on overpressure measuring in combustion chamber. burner plate serves for Setting the regulation elements: - regulation thermostat stage I.
„ The Operation and installation manual is a part of delivery in case that a equithermal regulation is required “. IMPORTANT WARNINGS : 1. The boiler after initiation works automatically. It only can be operated by adult persons familiar with this manual and the burner operation manual. 2. The boiler must be operated according to the manual and related standards. 3. The air of combustion must not contain a high moisture and dustiness.
6. A careful closing of the burner plate with the burner , the sealing plate and all small covers – check their tightness. 7. Mount the holder with explosion shutter. 8. Open the fuel supply; connection to el.network and boiler start-up. 9. Check the tightness of fuel supply to the burner . 10. Setting and adjusting of boiler heat output. 9.
For size 11 – 14 sections For size 5 – 10 sections
1 – jacket front section 2 – front section 3 – central section 4 – rear section 5 – boiler insertion 6 – anchor bolt 7 – plug with external thread 8 – thermomanometer clack valve 9 – sealing plate 10 – insul. adapting piece 11 – burner plate 12 – insul.
Information for customer Packaging edentification Assessment reference PE Plastic sacks, folie, corrugaled board, iron and plastic fix line Identification od principál materials used. Paper, Polyethylene, iron, wood Part 1: Summary of assessment Standard/Report Assessment requirement 1.1 Prevention by source reduction 1.2 Heavy metals and ensure below maximum permitted levels for components (CR 13695-1:2000) 1.