Product specifications

For an Indoor or Outdoor Pendant Model Installation
Refer to Figure 19 customer interface boards for indoor or outdoor pendant model mount cable installation
details.
1. Route each cable from the inside top of the housing.
2. Remove terminal blocks from the accessory kit. The 2-pin is for power, the two (2) 8-pin are for alarms
and control/relay; the 3-pin is for UTP option.
3. Strip approximately 1 inch (25 mm) of the cable outer jacket used for power, control, UTP video (optional)
alarms and relays. Then strip approximately 0.25 inches (6 mm) of insulation off of each individual wire.
4. Terminate the video (coaxial) cable with a BNC type male connector. Terminate the 8-conductor alarm
cable and the relay/control signal cable.
5. Make all connections to terminal blocks TB1 (power), TB2 (alarms), TB3 (relays/control signals) and TB4
(UTP video) with reference to Tables 2A, 2B, 2C, depending on version. On TB3, the COMMAND IN +
(COMM IN +) and COMMAND IN - (COMM IN -) connections must be used for simplex operation. For
half duplex operation, the additional signals RESPONSE OUT + (RESP OUT +) and RESPONSE OUT -
(RESP OUT -) must also be used.
6. Slide excess cable back up into the mount/pipe so that cable length is flush with the bottom of the
housing, approximately 8 to 9 inches (203 to 229 mm).
7. Install the terminal blocks TB1, TB2, TB3 and TB4 into the customer interface board at the proper block
frames. Install the video BNC cable connector to the customer interface board’s mating BNC connector.
ALTERNATE CONNECTION: For the models using the UTP video connection, use the twisted-pair video
wires. Attach each wire to screw terminal TB4. This signal is polarized and specific wire connections
(+ or -) are marked on the board. Refer to the instructions supplied with the receiver for those
connections. For fiber version, use standard ST connector on “daughter board.” For ViconNet, connect an
RJ-45 connector to J1 on the board.
XX134-08-01 Rev 209 SurveyorVFT Camera Dome System 5BWiring 31