4. Ensure that at least one thermostat is within 30 feet of the VWG for every cluster of 10 thermostats
installed.
5. Always try to locate if possible the VWG near the center of all associated wireless thermostats.
6. Always try to locate the VWG near on in line of sigh to as many wireless thermostats as possible.
7. Try to avoid metal, brick walls or concrete obstructions between wireless devices as much as
possible.
8. Make sure the antenna on the VWG is always perpendicular to the floor.
9. Avoid placing VWG and thermostats near metal or enclosed in metal boxes. If the VWG needs to be
installed inside a metal cabinet, use the remote antenna accessory.
Ex. 30 wireless thermostats total. A minimum of 3 of them should be within 30 feet ( 9 M ) of the VWG range.
30 feet
(
9 M
)
At least 1 Viconics thermostat node
to be within 30 feet ( 9 M ) of the
VWG for every other 10 thermostat
installed
v