Install Instructions

8 | PIR Ready VT7200 Series-Installation Guide
Analog control VT7200F5x00(x)
Typical applications
Schematic
Wiring
Settings
Pressure dependent VAV cooling only:VT7200C5x00(x) Floating actuator
Mandatory
Out1Conf = 2.0
CntrltTyp = Floating
FL time = as per
actuator
SeqOpera = 0
Cooling only
Pressure dependent VAV cooling only: VT7200F5x00(x) Analog actuator
Mandatory
Out1Conf = 2.0
RA/DA = as per
actuator
SeqOpera = 0
Cooling only
Heating / Cooling valve
Com
24 VAC
0-10 VDC
24 V~ Hot
24 V~ Com
AO 1
24 V~ Hot
24 V~ Com
AO 2
AO 1
Com
24 VAC
0-10 VDC
Heating valve
Cooling valve
Com
24 VAC
0-10 VDC
UI3 COS
0 V~ Com
24 V~ Hot
BO1 Open
BO2 Close
& Maximum
Position
the actuator
Modulating Floating
VAV Actuator
Analog VAV Actuator
& Maximum
Position
the actuator
0 to 10
VDC
UI3 COS
0 V~ Com
24 V~ Hot
AO1
Minimum
Minimum
Adjusted on
Room Temperature Control
Adjusted on
Room Temperature Control