Install Instructions

5 | 028-0485-00 November 2017
BI 1
Binary input #1 function:
Remote NSB timer clock input. The scheduling will now be set as per the binary input. It
provides low cost setback operation via a dry contact:
Contact opened = Occupied
Contact closed = Unoccupied
UI 3
Supply air sensor: Used for supply air temperature control.
TERMINAL IDENTIFICATION AND FUNCTION
Pin Number
Description
4
Power 24 Vac
5
Common
6
Do not use
7
24 Vac pulsed output
9
0 to 10 Vdc analog output
10
8 Vdc pulsed output
12
Night setback input
13
Remote sensor
14
Sensor common
16
Supply sensor