Install Instructions
13 | PIR Ready VT7300 Series-Installation Guide 
Temperature vs. resistance chart for 10 Kohm NTC thermistor (R
25°C 
= 10K±3%, B
25/85°C
= 3975K±1.5%)   
ºC 
ºF 
Kohm 
ºC 
ºF 
Kohm 
ºC 
ºF 
Kohm 
ºC 
ºF 
Kohm 
ºC 
ºF 
Koh
m 
-
40 
-40 
324.3197 
-20 
-4 
94.5149 
0 
32 
32.1910 
20 
68 
12.4601 
40 
104 
5.3467 
-
35 
-31 
234.4009 
-15 
5 
71.2430 
5 
41 
25.1119 
25 
77 
10.0000 
45 
113 
4.3881 
-
30 
-22 
171.3474 
-10 
14 
54.1988 
10 
50 
19.7390 
30 
86 
8.0694 
50 
122 
3.6202 
-
25 
-13 
126.6109 
-5 
23 
41.5956 
15 
59 
15.6286 
35 
95 
6.5499 
55 
131 
3.0016 
Status display 
The VT7300 series wall-mount Terminal Equipment Controller features a two-line, eight-
character display. There is a low level backlight level that is always active and can only be 
seen at night. 
When left unattended, the Terminal Equipment Controller has an auto scrolling display that 
shows the  actual status of the system.  There  is an option in the configuration menu to 
lockout  the  scrolling  display and to  only present  the room temperature  and conditional 
outdoor temperature to the user. With this option enabled, no local status is given of mode, 
occupancy and relative humidity. 
Each item is scrolled one by one with the back lighting in low level mode. Pressing any key 
will cause the back light to come on to high level. When left unattended for 10 seconds after 
changes are made, the display will resume automatic status display scrolling. 
To turn on the back light to high level, press any key on the front panel. The back lit display 
will return to low level when the Terminal Equipment Controller is left unattended for 45 
seconds. 
Sequence of auto-scroll status display: 
ROOM & 
HUMIDITY 
SYSTEM 
MODE 
SCHEDULE 
STATUS 
OUTDOOR 
TEMPERATURE 
ALARMS 
x.x °C or °F 
XX % RH 
Sys mode 
auto 
Occupied 
Outdoor 
x.x °C or °F 
Service 
If humidity 
display enabled 
Sys mode  
cool 
Stand-By 
Network value only 
Filter 
RoomTemp 
x.x °C or °F 
Sys mode 
heat 
Unoccup 
n/a 
Window 
If humidity 
display is not 
enabled 
Sys mode  
off 
Override 
n/a 
% RH display is conditional to: 
(Humidity display is model and configuration dependent) 
  Model with RH sensor built in 
  Display function can be enabled with RH display parameter. Displayed range is 
10 to 90 % RH 
Outdoor air temperature 
  Display is only enabled when outdoor air temperature network variable is 
received. 
Occupancy status 