Install Instructions
22 | PIR Ready VT7300 Series-Installation Guide 
BI 1 
Binary input no.1 
configuration 
Default value = None 
(None): No function will be associated with the input. 
Input can be used for remote network monitoring. 
(Rem NSB): remote NSB timer clock input. The 
scheduling will now be set as per the binary input. It 
provides low cost setback operation via a dry contact 
  Contact opened = Occupied 
  Contact closed = Unoccupied 
(Motion NO) or (Motion NC): Advanced PIR 
occupancy functions using a Normally Open (NO) or 
Normally Closed (NC) remote PIR motion sensor. 
Occupancy mode is now set as per applied PIR 
function and configuration. Application information and 
examples are available in document: APP-PIR-Guide-
Exx. This document will provide the installers and 
system designers with detailed examples on 
applications, parameter configuration information, 
sequence of operation, troubleshooting and diagnostic 
help required for the proper usage of the PIR 
accessory covers 
(Window) EMS: Forces the system to disable any 
current heating or cooling action by the Terminal 
Equipment Controller. The mode stays the same and 
the current setpoints are the same Occupied setpoints. 
Only the outputs are disabled. There is a Door/Window 
alarm displayed on the Terminal Equipment Controller 
to indicate to the local tenant that the door/window 
needs to be closed for cooling or heating to resume. 
  Contact opened = Window Opened 
  Contact closed = Window Closed 
*These settings will disable the local override function on the 
Terminal Equipment Controller 
