22 | PIR Ready VT7300 Series-Installation Guide
BI 1
Binary input no.1
configuration
Default value = None
(None): No function will be associated with the input.
Input can be used for remote network monitoring.
(Rem NSB): remote NSB timer clock input. The
scheduling will now be set as per the binary input. It
provides low cost setback operation via a dry contact
Contact opened = Occupied
Contact closed = Unoccupied
(Motion NO) or (Motion NC): Advanced PIR
occupancy functions using a Normally Open (NO) or
Normally Closed (NC) remote PIR motion sensor.
Occupancy mode is now set as per applied PIR
function and configuration. Application information and
examples are available in document: APP-PIR-Guide-
Exx. This document will provide the installers and
system designers with detailed examples on
applications, parameter configuration information,
sequence of operation, troubleshooting and diagnostic
help required for the proper usage of the PIR
accessory covers
(Window) EMS: Forces the system to disable any
current heating or cooling action by the Terminal
Equipment Controller. The mode stays the same and
the current setpoints are the same Occupied setpoints.
Only the outputs are disabled. There is a Door/Window
alarm displayed on the Terminal Equipment Controller
to indicate to the local tenant that the door/window
needs to be closed for cooling or heating to resume.
Contact opened = Window Opened
Contact closed = Window Closed
*These settings will disable the local override function on the
Terminal Equipment Controller