VT8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller CONTENTS Home Screen Display How to Enter Setup Screen Setup Screen Display ClockSettings Schedule Settings Occupancy Settings Network Settings Wireless Ecosystem Lua Settings ZigBee® Network Settings BACnet® Network Settings BACnet® Instance Number Configuration Parameters Setpoints Settings Display Settings User HMI - Hospitality User HMI - Commercial Other Functions Setpoint Adjustment Service Views Test Outp
User Interface Guide VT8600 Series HMI Display The below shows a typical user interface for the hospitality industry. The User HMI is configurable and allows display functions such as Date, Time, Outdoor Temperature, and Setpoint to be enabled or disabled by setting various parameters.
User Interface Guide 3 VT8600 Series Enter Set-up Screen Touch and hold this point for 3 seconds to enter setup mode Note: If a configuration/installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt shows to prevent access to device configuration components.
User Interface Guide VT8600 Series SET-UP SCREEN DISPLAY 2/2 2/ 2 Set u p Cl o ck - Sch ed u le Enter Schedule menu screen Wi rel ess Eco sy s t e m Enter Wireless Ecosystem menu screen (ZigBee wireless adapter module required) Enter Lua script settings (Lua script required) LUA SCHEDULE MENU SCREEN Cl o ck Enter Clock settings Sched u l e Enter Schedule settings Occ u p an cy Enter Occupancy settings Touch and hold this point for 3 seconds to enter the Schedule Menu screen.
User Interface Guide 5 VT8600 Series CLOCK SETTINGS The Clock settings screen allows the device’s internal time settings to be changed, including current time, standard day, month, year and weekday options, as well as choice between a 12 hour AM / PM display or a 24 hour display. Cl oc k Tim e f or m a t Time AM - P M --:-- Ye a r 2000 Month J a n.
User Interface Guide VT8600 Series SCHEDULE SETTINGS There are 7 different schedule setting screens, one for each day of the week, titled accordingly. Each day can have different scheduled events where the room controller is set to Occupied status or back to Unoccupied status and use the appropriate setpoints, back and forth up to 3 times per day.
User Interface Guide 7 VT8600 Series OCCUPANCY SETTINGS The occupancy settings screen allows you to determine how the Room Controller will determine whether it is functioning in Occupied or Unoccupied mode. Oc c u p a n c y O cc u p a n c y c md Loc occ. PARAMETER DETAILS Configuration parameters default value Occupancy cmd Default value: Local occ Significance and adjustments Occupancy Command Loc occ: occupancy is determined by local sequences (PIR or Schedule as configured under Occ. source).
User Interface Guide VT8600 Series WIRELESS ECOSYSTEM When wireless sensors are set up to communicate with a room controller, the functioning of each such sensor is described in a separate Zone screen, up to a maximum of 10 Zones. Select the appropriate type of sensor based on the required functioning using the up and down arrow keys.
User Interface Guide 9 VT8600 Series LUA SETTINGS The LUA settings screens show information about any custom LUA script uploaded to the controller. LUA scripts are not programmable on the controllers, and so must be uploaded to the controllers. 1/3 LUA L UA p r o g ram ’s n a m e : User p ro g r a m P ro g r a m : i f no t i n i t t h en init=true d el a y = 0 en d i f M E . B V1 = = 1 t h e n ME.
User Interface Guide VT8600 Series LUA GENERIC PARAMETERS The LUA settings include six generic parameters that do not have predefined values. These can be used to represent LUA script variables. They are user configurable in their default state, but when they are assigned a value by a LUA script they become read only, and the display colour of the parameter changes to red. These parameters are also modifiable through BACnet as Analog Values (AVs).
User Interface Guide 11 VT8600 Series ZIGBEE PRO NETWORK SETTINGS The ZigBee Pro set-up screen shows when a ZigBee card is detected in the model. Select the desired parameter and use up or down arrows to set the parameter to the desired value. 1/3 Zigbee network COM address 254 Node type Router ZigBee PAN ID 25 ZigBee channel 15 ZigBee short 0x0000 ZigBee status No NWK Previous Next Page Page ZigBee® Pro short address. The address is generated once the device joins a ZigBee® network.
User Interface Guide VT8600 Series PARAMETER DETAILS Configuration parameters default value ZigBee Pan ID Personal Area Network Identification Default value: 0 Range value: 1 - 1000 Significance and adjustments ZigBee Pro PAN ID Links specific Terminal Equipment Controllers to specific ZigBee® Pro coordinators. For every Terminal Equipment Controller reporting to a coordinator. Ensure set the SAME channel value both on the coordinator and the Terminal Equipment Controller(s).
User Interface Guide 13 VT8600 Series 2/3 Zigbee network Door contact status if installed Window contact status if installed Battery status of wireless switch D o o r st atus Closed D o o r in stalled No Win d o w status Closed Win . in stalled No L o w b at. alarm Off Perm it join On Indicates if door contact is installed Indicates if window contact is installed Automatically allows ZigBee® Pro devices to join the network through this controller.
User Interface Guide VT8600 Series BACNET NETWORK SETTINGS BACnet network set-up screen shows when BACnet is detected in model. Select desired parameter and use up or down arrow to set parameter to desired value. 1/2 B ACnet network Imperial or Metric units Baud rate settings C O M ad dress 254 N et w o rk units SI N et w o rk lang. English B au d rate Auto B A C n et status Offline 254 value sets BACnet® network Offline.
User Interface Guide 15 VT8600 Series BACNET INSTANCE NUMBER The default BACnet® instance number is generated by the model number and COM address of the controller. For example, the instance number of a VT8600A5500B with a COM address of 57 is generated as “86057”. The default instance number appears first. To change the instance number, use number pad and press Accept and save. Press Reset to automatic instance addressing to reset to automatic instance addressing.
User Interface Guide VT8600 Series CONFIGURATION PARAMETERS SCREEN 1/10 1/10 Configuration U I 1 6 co n fig No n e U I 1 7 c o n fig No n e U I 1 9 co n fig No n e S m ar t r ec o ve r y Off S e t p o in t fu n c . Attac h SP Mo de b u tto n No r ma l PARAMETER DETAILS SCREEN 1/10 Configuration parameters default value UI 16 Universal input no.1 configuration Default value: None Significance and adjustments Universal Input No. 1 None: No function will be associated with the input.
User Interface Guide 17 VT8600 Series PARAMETER DETAILS SCREEN 1/10 Configuration parameters default value UI 17 Universal input no.2 configuration Default value: None Significance and adjustments Universal Input No. 2 None: No function will be associated with the input. Input can be used for remote network monitoring. Door Dry: This configuration is only functional if universal input 16 is set to Motion NO or Motion NC or an onboard PIR sensor is used.
User Interface Guide VT8600 Series CONFIGURATION PARAMETERS SCREEN 2/10 2/10 Configuration F an cont. heat Off F an delay On St andy mode Absolute St andby diff. 2.0 °C Po wer-up delay 10 Sec. O cc upancy src Motion PARAMETER DETAILS SCREEN 2/10 Configuration parameters default value Fan cont. heat Fan control Default value: On Significance and adjustments Fan control in heating mode.
User Interface Guide 19 VT8600 Series PARAMETER DETAILS SCREEN 2/10 Configuration parameters default value Significance and adjustments Standby diff. Standby Difference Default value: 2 °C ( 3 °F ) When Standby mode is Offset, standby setpoints are calculated as: Standby cool = Cool setpoint + Standby diff. Standby heat = Heat setpoint - Standby diff. Adjustable from 0.5 a 2.
User Interface Guide VT8600 Series CONFIGURATION PARAMETERS SCREEN 3/10 3/10 Configuration St andby time 0.5 hrs U n o c c. time 0.0 hrs Temp. occ. time 2.0 hrs D eh . hysteresis 5 %RH D eh . lockout Enabled These parameters are only displayed on models with built in humidity sensor PARAMETER DETAILS SCREEN 3/10 Configuration parameters default value Standby time Default value: 0.
User Interface Guide 21 VT8600 Series PARAMETER DETAILS SCREEN 3/10 Configuration parameters default value Deh. hysteresis Default value: 5% RH Significance and adjustments Humidity Control Hysteresis Used only if dehumidification sequence is enabled: Range: 2 to 20% RH Models with humidity sensor only. Deh. lockout Default value: Enabled Dehumidification Lockout Typically toggled through the network.
User Interface Guide VT8600 Series CONFIGURATION PARAMETERS SCREEN 4/10 4/10 Configuration C o oling CPH 4 H eating CPH 4 F ro st protec. Off B O 1 aux. config NO A n t i short cycle 2 min M in sup. heat 18.0 °C PARAMETER DETAILS SCREEN 4/10 Configuration parameters default value Cooling CPH Cooling stages cycles per hour. Default value: 4 CPH Significance and adjustments Sets the maximum number of cooling stage cycles per hour under normal control operation.
User Interface Guide 23 VT8600 Series PARAMETER DETAILS SCREEN 4/10 Configuration parameters default value BO1 aux config Default value: NO Significance and adjustments Binary Output Terminal Output directly follows occupancy of the Terminal Equipment Controller. 1) NO: Occ or St-By = Contact Closed / Unoccupied = Contact Opened 2) NC: Occ or St-By = Contact Opened / Unoccupied = Contact Closed. Output to follow directly main occupancy and Fan on command.
User Interface Guide VT8600 Series CONFIGURATION PARAMETERS SCREEN 5/10 5/10 Configuration Prop. band 3.0 H ea t stages 2 C o ol stages 2 Econo. config Off C h angeover SP 13.0 °C M ec h. cooling Off PARAMETER DETAILS SCREEN 5/10 Configuration parameters default value Prop. band Default value: 3.0 Significance and adjustments Proportional Band Setting Adjusts proportional band used by the Terminal Equipment Controller PI control loop. Note: default value of 3.
User Interface Guide 25 VT8600 Series PARAMETER DETAILS SCREEN 5/10 Configuration parameters default value Significance and adjustments Heat stages Number of heating stages. Applicable to 2 stage models only Default value: 2 stages Will revert the operation of 2 stages Terminal Equipment Controller to single stage operation only when the second heating step is not needed.
User Interface Guide VT8600 Series CONFIGURATION PARAMETERS SCREEN 6/10 6/10 Configuration H ea t lockout 49.0 °C C o ol lockout -40.0 °C D is charge HL 49 °C D is charge LL 7 °C SH lockout 0 °C FA range 0 l/s PARAMETER DETAILS SCREEN 6/10 Significance and adjustments Heat lockout Outside air temperature heating lockout Default value: 120 °F (49 °C) Disables heating stage operation based on outdoor air temperature.
User Interface Guide 27 VT8600 Series CONFIGURATION PARAMETERS SCREEN 7/10 7/10 Configuration Econo min pos 0 % Econo max pos 100 % M in fresh air 0 l/s M ax fresh air 0 l/s M in CO2 800 ppm M ax CO2 1200 ppm PARAMETER DETAILS SCREEN 7/10 Configuration parameters default value Significance and adjustments Econo min pos Minimum Fresh Air Damper/Economizer Position Default value: 0% Minimum fresh air damper position. Effective only in Occupied mode (Fan is ON).
User Interface Guide VT8600 Series PARAMETER DETAILS SCREEN 7/10 Configuration parameters default value Min fresh air Minimum Fresh Air Value Default value: 0 CFM Significance and adjustments Minimum fresh air required. Effective only in Occupied mode (Fan is ON). This value is used to determine the fresh air damper position based on the Min/Max CO2 and Min/Max FA values (if FA Range is set to other than 0 CFM). See Fresh Air Damper Position section for more details.
User Interface Guide 29 VT8600 Series CONFIGURATION PARAMETERS SCREEN 8/10 8/10 Configuration Ap p l i c a t i o n Rooftop Hi gh B P 3 2 . 0 °C Low BP - 2 4 . 5 °C Co mf . o r e c o n . C o mf o r t Re v. v a l v e O Co m p . i n t e r l o c k Off PARAMETER DETAILS SCREEN 8/10 Configuration parameters default value Application Significance and adjustments Controls whether the operating logic for a rooftop application or a heat pump application is used.
User Interface Guide VT8600 Series PARAMETER DETAILS SCREEN 8/10 Configuration parameters default value Comfort/eco Comfort or economy mode Default value = Comfort Significance and adjustments Sets the operation and interaction mode of the heat pump with the auxiliary heat. Comfort mode: In Heating mode. If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat will be energized to satisfy the same heating setpoint. Economy mode: In Heating mode.
User Interface Guide 31 VT8600 Series CONFIGURATION PARAMETERS SCREEN 9/10 9/10 Configuration M ain password 0 U se r password 0 Schedule menu Enabled C ali b. temp. 0.0 °C C ali b. OS temp. 0.0 °C C ali b. humid. 0.0 %RH These parameters are only displayed on models with built in humidity sensor PARAMETER DETAILS SCREEN 9/10 Configuration parameters default value Main password Default value: 0 Significance and adjustments Main Password Installer password.
User Interface Guide VT8600 Series CONFIGURATION PARAMETERS SCREEN 10/10 1 0/10 Reinitialization Erase all? No A re you sure? No Pu sh to accept: PARAMETER DETAILS SCREEN 10/10 Configuration parameters default value Are you sure? Default value: No Viconics Technologies Inc.
User Interface Guide 33 VT8600 Series PASSWORD SETTINGS The following shows you how to set-up the password for the Installer and User Installer Password Installer Password Enter the code 1. 2. 3. 4. 0 1 2 3 4 5 6 7 8 9 Installer password prompt shows only if password value is greater than 0000. A password value of 0000 disables installer password but does not restrict access to configuration options. Installer password prompt automatically disappears after 10 seconds if no value is entered.
User Interface Guide VT8600 Series User Password Installer Password 1. 2. 3. 4. User password prompt shows only if password value is greater than 0000. A password value of 0000 disables user password but does not restrict access to local user functions. User password prompt automatically disappears after 10 seconds if no value is entered. User is permitted access to controller interface to change any allowed settings when correct password is entered.
User Interface Guide 35 VT8600 Series SETPOINT SETTINGS 1/2 1/2 Setpoints U n occ. cool 26.5 °C St andby cool 25.5 °C O cc. cool 24.0 °C O cc. heat 22.0 °C St andby heat 20.5 °C U n occ. heat 16.5 °C SETPOINT PARAMETER DETAILS Configuration parameters default value Significance and adjustments Unocc. cool Default value: 26.5 °C (80 °F) Unoccupied Cooling Standby cool Default value: 25.5 °C (78 °F) Standby Cooling Unoccupied cooling setpoint range: 2.0 to 37.5 °C (54 to 100 °F).
User Interface Guide VT8600 Series SETPOINT SETTINGS 2/2 2/2 Setpoints D ef ault heat 22.0 °C M in. deadband 1.5 °C M ax . heating 32.0 °C M in. cooling 12.0 °C Su pply air SP 13.0 °C D ehum. SP 50 %RH Parameter only displayed on models with built in humidity sensor. SETPOINT PARAMETER DETAILS Configuration parameters default value Default heat Default value: 22.0 °C (73 °F) Significance and adjustments Default Heat Used for hospitality applications in stand-alone mode only.
User Interface Guide 37 VT8600 Series DISPLAY SETTINGS 1/2 1/2 Display U ser HMI 0 C o lour White M ain display Temp. St andby screen No C o ntrast 0 DISPLAY PARAMETER DETAILS Configuration parameters default value User HMI Default value: 0 Significance and adjustments User HMI Select user HMI type. Range: 0 to 11. Colour Default value: White White Main display Default value: Temp.
User Interface Guide VT8600 Series User HMI Hospitality 0 • • • • • • Setpoint adjustment System mode setting Fan mode setting Local unit scale adjustment Local user language User help menu Hospitality 1 • • • • Setpoint adjustment System mode setting Fan mode setting User help menu Hospitality 2 • • • Local unit scale adjustment Local user language User help menu Hospitality 3 • • Setpoint adjustment User help menu Parameters are model dependent and may not appear on certain models.
User Interface Guide Commercial 8 • • • • Setpoint adjustment Unoccupied mode override Local user language User help menu 39 VT8600 Series Commercial 9 • • • Setpoint adjustment Unoccupied mode override User help menu Commercial 10 • • • Setpoint adjustment Unoccupied mode override User help menu Commercial 11 • • • • Setpoint adjustment System mode setting Unoccupied mode override User help menu Note: The day/night setback button appears only in unoccupied mode in the Commercial HMIs 7 to 11
User Interface Guide VT8600 Series Heating only configuration Setpoint value shows if main display parameter is set to Setpoint. Time and Date show only when a network time synchronisation command is received. On/Off icon is used instead of system mode icon when sequence of operation is set to either heating on or cooling only. Setpoint adjustment for cooling mode In Cooling mode, the setpoint displayed in the bar is the current occupied cooling setpoint.
User Interface Guide 41 VT8600 Series Setpoint adjustment for heating mode In automatic mode, setpoint showing at the top of the set point bar located directly under the blue line represents the actual occupied cooling setpoint. During occupied setpoints adjustment, large digits are temporarily used to display the occupied Cooling Setpoint or occupied Heating Setpoint. The actual setpoint is dependent on the last effective demand (heating or cooling).
User Interface Guide VT8600 Series CUSTOMIZABLE COLOR OPTIONS Green Dark Grey Grey Viconics Technologies Inc. 028-0441-01 Blue 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 www.viconics.com © 2015 Viconics Technologies. All rights reserved.
User Interface Guide 43 VT8600 Series DISPLAY SETTINGS 2/2 2/2 Display Language English Units °C Low backlight 60 % Night backlight 5% RH display Disable These parameters are only displayed on models with built in humidity sensor DISPLAY PARAMETER DETAILS Configuration parameters default value Language Default value: English Significance and adjustments Language Select language for main display.
User Interface Guide VT8600 Series DISPLAY PARAMETER DETAILS Configuration parameters default value Night backlight Default value: 5% Significance and adjustments Night Backlight Display Set display backlight intensity after 2 minutes of keyboard inactivity. Adjustable: 0 to 100%. Parameter only available for models with motion/light detectors. The screen backlight progressively decreases down to this setting when room is dark.
User Interface Guide 45 VT8600 Series SERVICE SCREEN VIEWS The service view screens show the current status of certain points locally at the controller. These points can also be viewed through the network. Service view allows service contractor to visualize the status of key functionality to correctly diagnose operational system issues. 1/7 Service view F irm w are rev. 1 .0 Firmware Revision R o o m t em p . xx.x °C Room Temperature C O 2 level 0 PPM CO2 Remote Sensor Level U I20 t em p . xx.
User Interface Guide VT8600 Series 3/7 Service view U I16 b in ary Not activ. Universal Input Status U I17 b in ary Not activ. Universal Input Status U I19 an alo g 0% Universal Input Status A irf lo w level 0 l/s Airflow Level Z ig b . PIR in st . Off External PIR Install Status Z ig b . sen s. m o t . No motion Local Motion Status Viconics Technologies Inc.
User Interface Guide 47 VT8600 Series 5/7 Service view F ro st alarm Off Frost Alarm Status R eco very st at u s Off Recovery Status L o cal m o t io n Off Local Motion Status D eh .
User Interface Guide VT8600 Series 7/7 Service view D evice n am e: Device Name / Model Number VT 86xxU 5x00B - xxx The Model Number is the BACnet® device name automatically assigned when using the current BACnet® addressing scheme based on the MAC address. The network can update and change the device BACnet® name. If changed, the new updated BACnet® device name shows on the screen. Viconics Technologies Inc. 028-0441-01 9245 Langelier Blvd.
User Interface Guide 49 VT8600 Series TEST OUTPUTS 1/2 Test Outputs B O 1 aux output Off G f an status Off Y1 status Off Y2 status Off W 1 status Off W 2 status Off Note 1: The test output screen allows manual override of specified outputs. When any BACnet® network priority array includes a value, the status background shows in red. After any output state is overridden, the command is cancelled after 1 minute of screen inactivity (auto exit to main screen) or when page is exited.
User Interface Guide VT8600 Series TEST OUTPUTS 2/2 Test outputs U O 10 analog 0.0 Vdc U O 11 analog 0.0 Vdc Note: screen Test outputs are LIVE. Any output gets displayed immediately for any value change according to the following: 1. If any BACnet priority array (1 - 16) includes a value, the displayed state background shows in red. 2. When toggling a value on the screen, the output directly energizes according to the selected value. 3.
User Interface Guide 51 VT8600 Series LANGUAGE SELECTION 2/4 Language selection F r en ch Enabled Bulgarian Disabled S p an i sh Enabled Czech Disabled C h i n ese E na b l e d Danish Disabled R u ssi an Enabled Dutch Disabled A r ab i c Disabled Finnish Disabled 3/ 4 L an g u ag e sel ec t i o n 4/4 Language selection G er m an Disabled Polish Disabled H u n g ar i an Disabled Portuguese Disabled I n d o n esi an Disabled Slovak Disabled I t al i an Disabled Swedish
User Interface Guide VT8600 Series APPENDIX A: TERMINAL CORRESPONDENCE The terminals of an VT8600 are identified differently and have a wider range of possible functions compared to those of any of the VT7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7000 series and the VT8600 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller with a VT8600 Room Controller.