User Guide

12
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-01 www.viconics.com April 2015
© 2015 Viconics Technologies. All rights reserved.
VT8600 SeriesUser Interface Guide
PARAMETER DETAILS
Conguration parameters default value Signicance and adjustments
ZigBee Pan ID
Personal Area Network
Identication
Default value: 0
Range value: 1 - 1000
ZigBee Pro PAN ID
Links specic Terminal Equipment Controllers to
specic ZigBee
®
Pro coordinators. For every Terminal Equipment
Controller reporting to a coordinator. Ensure set the SAME
channel value both on the coordinator and the Terminal
Equipment Controller(s).
Default value of 0 is NOT a valid PAN ID. The valid range of
available PAN ID is from 1 to 1000.
Range 1 to 500 for centralized networked applications using a
ZigBee
®
Pro Coordinator.
Range 501 to 1000 is for stand-alone applications where each
controller is its own coordinator for stand alone installation of
wireless door and window switches.
ZigBee channel
Channel selection
Default value: 10
Range value: 11 - 25
ZigBee channel
This parameter links specic Terminal Equipment Controllers to
specic ZigBee
®
Pro coordinators. For every Terminal Equipment
Controller reporting to a coordinator, ensure you set the
SAME channel value both on the coordinator and the Terminal
Equipment Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range
of available channel is from 11 to 25.
ZigBee status
Read only
ZigBee status
The following read only messages show in this eld:
(Not Det): ZigBee
®
Pro module not detected
(Pwr On): ZigBee
®
Pro module detected but not congured
(No NWK): ZigBee
®
Pro congured but no network joined
(Joined): ZigBee
®
Pro network joined
(Online): Communicating