User Guide

16
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-01 www.viconics.com April 2015
© 2015 Viconics Technologies. All rights reserved.
VT8600 SeriesUser Interface Guide
PARAMETER DETAILS SCREEN 1/10
Conguration parameters default value Signicance and adjustments
UI 16
Universal input no.1 conguration
Default value: None
Universal Input No. 1
None: No function will be associated with the input. Input can be
used for remote network monitoring.
Rem NSB: remote NSB timer clock input. The scheduling will
now be set as per the binary input. It provides low cost setback
operation via a dry contact
Contact opened = Occupied
Contact closed = Unoccupied
Window: Forces the system to disable any current heating or
cooling action by the Terminal Equipment Controller. The mode
stays the same and the current setpoints are the same occupied
setpoints. Only the outputs are disabled. There is a Door/
Window alarm displayed on the Terminal Equipment Controller
to indicate to the local tenant that the door/window needs to be
closed for cooling or heating to resume. Use NC contact.
Contact opened = System disabled with local Window alarm
Contact closed = System enabled
Service: a service alarm shows on the Terminal Equipment
Controller LCD screen when input is energized.
Fan lock: a fan lock alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is not
energized.
Open contact = no airow
Closed contacts = airow present
1/10 Configuration
UI19 config
UI17 config
UI16 config
None
None
None
Smart recovery
Off
Setpoint func.
Attach SP
Mode button
Normal
CONFIGURATION PARAMETERS SCREEN 1/10