I-P500 FIELD INSTALLATION HANDBOOK I-P500 FIELD INSTALLATION HANDBOOK Vic-Press SCHEDULE 10S SYSTEM PRODUCTS ™ • O-RING INFORMATION • PIPE PREPARATION • PRODUCT INSTALLATION WARNING • Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic products. • Depressurize and drain piping systems before attempting to install, remove, adjust, or maintain any Victaulic products. • Wear safety glasses, hardhat, foot protection, and hearing protection.
Table of Contents GENERAL INFORMATION HAZARD IDENTIFICATION.................................................................2 INTRODUCTION................................................................................3 IMPORTANT INFORMATION..............................................................4 ASTM A-312 Types 304/304L and 316/316L Schedules 5S and 10S Stainless Steel Pipe........................... 4 Seal Selection...........................................................................
IMPORTANT LUBRICATION INFORMATION.....................................18 Handling of Product That IS Pre-Lubricated.............................18 Handling of Product That IS NOT Pre-Lubricated.....................18 PRODUCT ASSEMBLY.....................................................................18 STYLES P540/P560 VIC-PRESS SCHEDULE 10S END PLUGS FOR FUTURE SYSTEM EXPANSION................................................20 Initial Installation of End Plug...............................................
General Information I-P500_1
HAZARD IDENTIFICATION Definitions for identifying the various hazard levels are provided below. This safety alert symbol indicates important safety messages. When you see this symbol, be alert to the possibility of personal injury. Carefully read and fully understand the message that follows. DANGER • The use of the word “DANGER” identifies an immediate hazard with a likelihood of death or serious personal injury if instructions, including recommended precautions, are not followed.
INTRODUCTION This field installation handbook is a basic field reference guide for Victaulic Vic-Press Schedule 10S System Products. This handbook provides easy reference to proper installation information.
IMPORTANT INFORMATION ASTM A-312 Types 304/304L and 316/316L Schedules 5S and 10S Stainless Steel Pipe Vic-Press Schedule 10S System Products are designed for joining ASTM A-312 Schedules 5S and 10S stainless steel pipe (Types 304/304L or 316/316L) in ½-inch/21.3-mm, 3/4-inch/26.9-mm, 1-inch/33.7-mm, 11/2-inch/48.3-mm, and 2-inch/60.3-mm sizes.
Seal Selection CAUTION • To ensure maximum product performance, always specify the proper grade seal for the intended service. Failure to select the proper grade seal for the service may cause joint failure, resulting in property damage. Many factors must be considered for optimum seal performance. Do not subject seals to temperatures beyond the recommended limits, since excessive temperatures will degrade seal life and performance.
PREVENTION OF STAINLESS STEEL CONTAMINATION These recommendations are provided as a general guideline to help prevent surface contamination of stainless steel products. Handling and Storage 1. Stainless steel products should be handled only with non-contaminating apparatus (i.e. nylon straps or apparatus protected with a non-contaminating buffer material). 2. If carbon steel straps are used, a buffer material must be placed between the strap and the stainless steel product.
PIPE SPECIFICATIONS ASTM A-312 Types 304/304L and 316/316L Schedule 5S Stainless Steel Pipe Pipe Dimensions and Weights Actual Pipe Outside Diameter inches/mm Maximum Outside Diameter Minimum Outside Diameter Nominal Inside Diameter inches/mm Nominal Wall Thickness inches/mm Approximate Weight of Pipe Per foot (lbs/kg) ½ 0.840 21.3 0.855 21.72 0.809 20.55 0.710 18.0 0.065 1.7 0.6 0.2 ¾ 1.050 26.9 1.065 27.05 1.019 25.88 0.920 23.4 0.065 1.7 0.7 0.3 1 1.315 33.7 1.330 33.78 1.284 32.
MINIMUM PIPE-NIPPLE LENGTH REQUIREMENTS WARNING • Pipe for use with Vic-Press Schedule 10S System Products must meet the minimum pipe-nipple length requirements specified in the table below. Failure to follow these instructions could cause improper product installation, resulting in serious personal injury and/or property damage. Actual Pipe Outside Diameter inches/mm Minimum Pipe-Nipple Length Required inches/mm ½ 0.840 21.3 3 1/8 79 ¾ 1.050 26.9 3 1/8 79 1 1.315 33.7 4 102 1½ 1.900 48.
Piping Support for ASTM A-312 Types 304/304L and 316/316L Schedule 5S Stainless Steel Pipe For ASTM A-312 Types 304/304L and 316/316L Schedule 5S stainless steel pipe, the maximum support spacing corresponds to ASME B31.1, B31.3, or B31.9, as noted, and must be used only in conjunction with Vic-Press Schedule 10S System Products. Pipe Size Suggested Maximum Span Between Supports – feet/meters Water Service Gas/Air Service Actual Pipe Outside Diameter inches/mm B31.1 B31.3 B31.9 B31.1 B31.3 B31.
OPERATOR SAFETY REQUIREMENTS FOR VICTAULIC PFT510 VIC-PRESS SCHEDULE 10S TOOLS NOTICE • Although Victaulic PFT510 Vic-Press Schedule 10S Tools for Vic-Press Schedule 10S System Products are manufactured for safe, dependable operation, it is impossible to anticipate the combinations of circumstances that could result in an accident. The following instructions are recommended for safe operation of Victaulic PFT510 Vic-Press Tools.
16. Always maintain tools. Keep tools clean for safe, dependable operation. Follow all cleaning and lubricating instructions and jaw maintenance instructions. Report any unsafe conditions to authorized personnel for immediate correction. 17. Check for damaged parts. Check for alignment of moving parts, breakage of parts, mounting, and other conditions that may affect tool or jaw operation. Parts that are damaged should be replaced by an authorized service center.
SPACE REQUIRED FOR THE PRESSING OPERATION - VICTAULIC PFT510 VIC-PRESS SCHEDULE 10S TOOL Assembly of Vic-Press Schedule 10S System Products requires sufficient space for opening the press jaws and placing them over the coupling or fitting. The tool must be perpendicular to the coupling or fitting and the connecting pipe. Table I Space Requirement Dimensions Actual Pipe Nominal Outside Diameter Diameter A B C inches inches/mm inches/mm inches/mm inches/mm ½ 0.840 21.3 1 3/4 44 4 102 4 1/2 114 ¾ 1.
Vic-Press Schedule 10S System Products for Schedules 5S and 10S Stainless Steel Pipe Installation Instructions I-P500_13
INSTALLATION REQUIREMENTS WARNING • Read and understand all instructions, including the operating and maintenance manual for the PFT510 Vic-Press Schedule 10S Tool, before attempting to install any Victaulic Vic-Press Schedule 10S System Products. • Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. • Wear safety glasses, hardhat, and foot protection.
PIPE PREPARATION ACCEPTABLE BURRS AND SHARP EDGES REMOVED Pipe ends shall be square cut. The pipe OD shall not contain burrs, sharp edges, raised weld beads, axial score marks, scratches, and indentations. NOT ACCEPTABLE Excessive chamfer on the pipe ID will cut the seal during product assembly. Excessive chamfer is not acceptable. NOT ACCEPTABLE Abrasive wheels and saws will leave edges on pipe ends that are especially pronounced on one side. Burrs and sharp edges are not acceptable.
MARKING THE PIPE CAUTION • Insertion depth must be measured and marked on the pipe ends to provide visual confirmation that the pipe is inserted fully into the fitting. Failure to follow this instruction could cause improper product assembly, resulting in joint leakage and/or property damage. Pipe insertion depth must be measured by using the Vic-Press Schedule 10S Marking Gauge or a ruler or tape measure.
Vic-Press Schedule 10S Slip Couplings Vic-Press Schedule 10S Slip Couplings do not contain a pipe stop so that insertion to various depths can be accommodated. For proper assembly, the pipe must be inserted into the fitting to the minimum depth listed in the “Vic-Press Schedule 10S Slip Coupling Minimum Insertion Depth Requirements” table below. 1. Refer to the “Vic-Press Schedule 10S Slip Coupling Minimum Insertion Depth Requirements” table below.
IMPORTANT LUBRICATION INFORMATION Handling of Product That IS Pre-Lubricated CAUTION • DO NOT remove the Vic-Press Schedule 10S System Product from the shipping bag until it is ready to be installed/pressed. • Handling and storage of product that is pre-lubricated is critical for ensuring proper product performance. Failure to follow instructions could cause dirt or debris accumulation on the pre-lubricated seals, resulting in pinching or tearing of seals, joint leakage, and property damage.
CAUTION • DO NOT force the pipe into the coupling or fitting. • Insert the pipe into the coupling or fitting with a slight twisting action to ease insertion. Forcing the pipe into position may cause damage to the seal, resulting in joint leakage and/or property damage. Standard Vic-Press Jaw for 1/2-inch/21.3-mm, 3/4-inch/26.9-mm, and 1-inch/33.7-mm Sizes 2. For Standard Couplings and Fittings: Insert the pipe into the coupling or fitting with a slight twisting action to ease insertion.
STYLES P540/P560 VIC-PRESS SCHEDULE 10S END PLUGS FOR FUTURE SYSTEM EXPANSION WARNING • Read and understand all instructions before attempting to install any Victaulic piping products. • Depressurize and drain the piping system before attempting to cut into an existing Vic-Press Schedule 10S system. • DO NOT use torches or other heat sources near Vic-Press Schedule 10S System Products. • Wear safety glasses, hardhat, and foot protection.
INSTRUCTIONS FOR SYSTEM EXPANSION WARNING • Depressurize and drain the piping system completely before attempting to cut into an existing system. Failure to follow this instruction could result in serious personal injury and property damage. 1. Depressurize and drain the piping system completely. 2. End plugs are provided with an indented end-cut-off score line for starting the cut with a saw.
End Plug Adjoining Fitting 6. Refer to the “Product Assembly” section of this handbook to install the adjoining Vic-Press Schedule 10S fitting. 7. Make sure the cut-off end of the end plug is inserted fully up to the mark made in step 5. Complete the installation by using the PFT510 Vic-Press Schedule 10S Tool. Always refer to the TM-PFT510 Operating and Maintenance Manual for detailed safety information and instructions for using the tool.
INSTALLATION INSPECTION WARNING • Always inspect each joint to ensure proper product installation. • Undersized or oversized pipe and improperly pressed fittings are unacceptable. Any of these conditions must be corrected before attempting to pressurize the system. Failure to follow these instructions could result in serious personal injury, property damage, joint leakage, and/or joint failure. Proper pipe preparation and proper pressing of couplings or fittings is essential for maximum joint performance.
I-P500_24
Product Data The following information contains center-to-end, end-to-end, take-out, and similar overall dimensions for Vic-Press Schedule 10S System Products. Refer to the current Victaulic submittal for complete dimensional information and for products not listed in this section. NOTICE • Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P507 and P597 – Standard Couplings (P x P) E to E U STYLES P507 AND P597 Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm E to E U Takeout 1/2 15 0.840 21.3 2.78 70.6 0.65 16.5 3/4 20 1.050 26.7 2.78 70.6 0.65 16.5 1 25 1.315 33.7 3.11 79.0 0.73 18.5 1 1/2 40 1.900 48.3 3.48 88.4 0.72 18.3 2 50 2.375 60.3 3.96 100.6 0.71 18.0 Styles P508 – Slip Coupling (P x P) I min. E to E I min.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles Styles Styles Styles P568 and P586 – 90° Elbows (P x P) P562 and P542 – 90° Street Elbows (P x T) P571 and P591 – 45° Elbows (P x P) P563 and P543 – 45° Street Elbows (P x T) C to P U C to T C U to P STYLES P568 AND P586 STYLES P562 AND P542 Styles P568 and P586 90° Elbows Size Styles P562 and P542 90° Street Elbows Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm C to P inches/mm U Takeout inches/mm C to P* inches/mm U Takeout inches/
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P572 and P592 – Tees (P x P x P) C to EOB U 2 C to P U1 STYLES P572 AND P592 Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm C to P U1 C to EOB U2 1/2 15 0.840 21.3 1.71 43.4 1.29 32.8 1.91 48.5 0.84 21.3 3/4 20 1.050 26.7 2.01 51.1 1.89 48.0 1.93 49.0 0.87 22.1 1 25 1.315 33.7 2.27 57.7 2.17 55.1 2.24 56.9 1.05 26.7 1 1/2 40 1.900 48.3 2.72 69.1 2.68 68.1 2.74 69.6 1.37 34.8 2 50 2.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P578 and P588 – Tees with Threaded Branch (P x P x F†) C to EOB U2 C to P U1 STYLES P578 AND P588 Size Dimensions – inches/mm Nominal Size inches/mm C to P U1 Takeout C to EOB U2 Takeout 1/2 15 × 1/2 15 × 1/2 15 1.71 43.4 1.29 32.8 1.46 37.1 0.93 23.6 3/4 20 × 3/4 20 × 1/2 15 2.01 51.1 1.89 48.0 1.57 39.9 1.04 26.4 3/4 20 2.01 51.1 1.89 48.0 1.56 39.6 1.02 25.9 1/2 15 2.27 57.7 2.17 55.1 1.70 43.2 1.17 29.7 3/4 20 2.27 57.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P573 and P593 – Tees with Reducing Branch (P x P x P) C to EOB U2 C to P U1 STYLES P573 AND P593 Size Dimensions – inches/mm Nominal Size inches/mm C to P U1 Takeout C to EOB U2 Takeout 3/4 20 × 3/4 20 × 1/2 15 2.01 51.1 1.89 48.0 2.01 51.1 0.95 24.1 1 25 × 1 25 × 1/2 15 2.27 57.7 2.17 55.1 2.14 54.4 1.08 27.4 3/4 20 2.27 57.7 2.17 55.1 2.07 52.6 1.00 25.4 1/2 15 2.72 69.1 2.69 68.3 2.44 62.0 1.17 29.7 3/4 20 2.72 69.1 2.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P560 and P540 – End Plugs for Future System Expansion E to E CL IL Insertion Mark End Cut-Off Line for Future System Expansion STYLES P560 AND P540 Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm E to E IL Insertion Length CL Cut-Off Line 1/2 15 0.840 21.3 4.00 101.6 1.06 26.9 0.50 12.7 3/4 20 1.050 26.7 4.00 101.6 1.06 26.9 0.50 12.7 1 25 1.315 33.7 4.38 111.3 1.19 30.2 0.50 12.7 1 1/2 40 1.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P576 and P596 – Male Threaded Adapters (P x M†) IL E to E U * STYLES P576 AND P596 Size Dimensions – inches/mm Nominal Size inches/mm E to E U Takeout IL Insertion Length 1/2 15 × 1/2 15 3.93 99.8 2.32 58.9 1.06 26.9 3/4 20 × 1/2 15 3.34 84.8 1.75 44.5 1.06 26.9 3/4 20 3.85 97.8 2.22 56.4 1.06 26.9 1 25 3/4 20 3.34 84.8 3.50 88.9 1.60 40.6 1.77 45.0 1.06 26.9 1.19 30.2 1 25 4.19 106.4 2.32 58.9 1.19 30.2 3/4 20 3.65 92.7 1.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P579 and P599 – Female Threaded Adapters (P x F†) IL E to E U * STYLES P579 AND P599 Size Dimensions – inches/mm Nominal Size inches/mm E to E U Takeout IL Insertion Length 1/2 15 × 1/2 15 2.39 60.7 0.79 20.1 1.06 26.9 3/4 20 × 1/2 15 2.31 58.7 0.71 18.0 1.06 26.9 3/4 20 2.31 58.7 0.79 20.1 1.06 26.9 1/2 15 2.47 62.7 0.75 19.1 1.19 30.2 3/4 20 2.47 62.7 0.73 18.5 1.19 30.2 1 25 2.60 66.0 0.88 22.4 1.19 30.2 1 25 2.92 74.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P585 and P584 – Threaded Unions (P x P) E to E U STYLES P585 AND P584 Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm E to E U Takeout 1/2 15 0.840 21.3 7.50 190.5 5.37 136.4 3/4 20 1.050 26.7 7.37 187.2 5.24 133.1 1 25 1.315 33.7 7.59 192.8 5.21 132.3 1 1/2 40 1.900 48.3 8.36 212.3 5.61 142.5 2 50 2.375 60.3 8.01 203.5 4.76 120.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Styles P566 and P565 – Van Stone Flange Adapters (P x L) E to E U STYLES P566 AND P565 Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm E to E U Takeout 1/2 15 0.840 21.3 3.37 85.6 2.30 58.4 3/4 20 1.050 26.7 3.29 83.6 2.22 56.4 1 25 1.315 33.7 3.45 87.6 2.26 57.4 1 1/2 40 1.900 48.3 3.61 91.7 2.22 56.4 2 50 2.375 60.3 4.55 115.6 2.92 74.
VIC-PRESS SCHEDULE 10S SYSTEM FITTINGS Style P561 – Weld Adapter (P x T) IL E to E U STYLE P561 Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm E to E U Takeout IL Insertion Length 1/2 15 0.840 21.3 3.92 99.6 2.85 72.4 1.06 26.9 3/4 20 1.050 26.7 3.84 97.5 2.77 70.4 1.06 26.9 1 25 1.315 33.7 4.18 106.2 3.00 76.2 1.19 30.2 1 1/2 40 1.900 48.3 4.37 111.0 2.98 75.7 1.38 35.1 2 50 2.375 60.3 4.85 123.2 3.22 81.8 1.63 41.
VIC-PRESS SCHEDULE 10S SYSTEM BALL VALVES Series P589 – Vic-Press Brass Body Ball Valve with Stainless Steel Vic-Press Schedule 10S Ends (P x P) C B D A SERIES P589 Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm A ± 0.125/ 3.18 B C D 1/2 15 0.840 21.3 9.030 229.36 1.42 36.1 3.03 77.0 1.06 26.9 3/4 20 1.050 26.7 9.120 234.65 1.90 48.3 3.74 95.0 1.06 26.9 1 25 1.315 33.7 10.108 256.74 2.05 52.1 3.74 95.0 1.19 30.2 1 1/2 40 1.900 48.3 11.
VIC-PRESS SCHEDULE 10S SYSTEM BALL VALVES Series P569 – Vic-Press Schedule 10S, Type 316 Stainless Steel Ball Valve E B C A VIC-PRESS SCHEDULE 10S X VIC-PRESS SCHEDULE 10S (P X P) Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm A End to End B C E 1/2 15 0.840 21.3 8.26 209.8 2.17 55.1 1.06 26.9 5.24 133.1 3/4 20 1.050 26.7 8.36 212.3 2.32 58.9 1.06 26.9 5.24 133.1 1 25 1.315 33.7 8.77 222.8 2.76 70.1 1.19 30.2 6.02 152.9 1 1/2 40 1.
VIC-PRESS SCHEDULE 10S SYSTEM BALL VALVES Series P569 – Vic-Press Schedule 10S, Type 316 Stainless Steel Ball Valve E B C A VIC-PRESS SCHEDULE 10S X GROOVE (P X G) Size Dimensions – inches/mm Nominal Size inches/mm Actual Pipe Outside Diameter inches/mm A End to End B C E 3/4 20 1.050 26.7 8.44 214.4 2.32 58.9 1.06 26.9 5.24 133.1 1 25 1.315 33.7 8.76 222.5 2.76 70.1 1.19 30.2 6.02 152.9 1 1/2 40 1.900 48.3 10.32 262.1 3.31 84.1 1.38 35.1 7.52 191.0 2 50 2.375 60.3 10.92 277.
I-P500_40
Helpful Information English and Metric Conversion Chart Decimal Equivalents of Fractions Minutes Converted to Decimals of a Degree Water Pressure to Feet-of-Head Feet-of-Head of Water to Pressure Where to Find Installation Instructions for Additional Products ENGLISH AND METRIC CONVERSION CHART Convert US to Metric 25.4 X inches (in) Convert Metric to US = millimeters (mm) X 0.03937 0.3048 X feet (ft) = meter (m) X 3.281 0.4536 X pounds (lbs) = kilograms (kg) X 2.205 28.35 X ounces (oz) = 6.
DECIMAL EQUIVALENTS OF FRACTIONS Fraction in inches Decimal Equivalent inches Decimal Equivalent millimeters Fraction in inches Decimal Equivalent inches Decimal Equivalent millimeters 1/64 1/32 3/64 1/16 5/64 3/32 7/64 1/8 9/64 5/32 11/64 3/16 13/64 7/32 15/64 1/4 17/64 9/32 19/64 5/16 21/64 1/3 11/32 23/64 3/8 25/64 13/32 27/64 7/16 29/64 15/32 1/2 0.016 0.031 0.047 0.063 0.781 0.094 0.109 0.125 0.141 0.156 0.172 0.188 0.203 0.219 0.234 0.250 0.266 0.281 0.297 0.313 0.328 0.333 0.344 0.359 0.375 0.
WATER PRESSURE TO FEET-OF-HEAD Pounds Per Square Inch Feet of Head Pounds Per Square Inch Feet of Head 1 2 3 4 5 6 7 8 9 10 15 20 25 30 40 50 60 70 80 90 2.31 4.62 6.93 9.24 11.54 13.85 16.16 18.47 20.78 23.09 34.63 46.18 57.72 69.27 92.36 115.45 138.54 161.63 184.72 207.81 100 110 120 130 140 150 160 170 180 200 250 300 350 400 500 600 700 800 900 1000 230.90 253.93 277.07 300.16 323.25 346.34 369.43 392.52 415.61 461.78 577.24 692.69 808.13 922.58 1154.48 1385.39 1616.30 1847.20 2078.10 2309.
WHERE TO FIND INSTALLATION INSTRUCTIONS FOR ADDITIONAL PRODUCTS The following table provides a listing of products and installation information. If you need additional copies of any installation information, contact Victaulic at 1-800-PICK VIC. NOTE: If two sources of instructions are referenced in this index, Victaulic recommends the use of both to ensure proper product installation.
Product Where to Find Instructions Series 731-D Suction Diffuser I-731D Series 731-I Suction Diffuser (Europe Only) I-731I/W731I Series W731-I AGS Suction Diffuser (Europe Only) I-731I/W731I Series 732 Vic-Strainer Wye Type I-730/732/AGS Series W732 AGS Vic-Strainer Wye Type I-730/732/AGS Series 747M FireLock Zone Control Riser Module Assembly I-747M Series 761 Vic-300 MasterSeal® Butterfly Valve I-VIC300MS and I-100 Series W761 AGS Vic-300 Butterfly Valve I-AGS.
Product Where to Find Instructions Style 77/77A/77S Flexible Coupling I-100 Style 77DX Flexible Stainless Steel Coupling for Duplex and Super Duplex Pipe I-100 Style W77 AGS Flexible Coupling I-W07/W77 and I-100 Style 78/78A Snap-Joint ® Coupling I-100 Style 89 Rigid Coupling for Stainless Steel IT-89 and I-100 Style W89 AGS Rigid Coupling for Stainless Steel I-W89 Style 99 Roust-A-Bout Coupling for PlainEnd Steel IT-99 and I-100 Style 107H/107 QuickVic Rigid Coupling for Steel Pipe I-107H/
Product Where to Find Instructions Style 735 Fire Pump Test Meter I-100 Style 738 TA Portable Differential Meter Instructions Shipped with Meter Style 739 Portable Master Meter Instructions Shipped with Meter Style 740 TA CBI Meter Instructions Shipped with Meter Style 741 NPS and Metric Vic-Flange Adapter I-100 Style W741 AGS Vic-Flange Adapter IT-W741 and I-100 Style 743 Vic-Flange Adapter I-100 Style 744 FireLock Flange Adapter I-100 Style 750 Reducing Coupling I-100 Style 770 Large-D
FIELD INSTALLATION HANDBOOK I-P500 VICTAULIC GLOBAL CONTACT INFORMATION US & WORLD HEADQUARTERS EUROPE P.O. Box 31 Easton, PA 18044-0031 USA Prijkelstraat 36 9810 Nazareth, Belgium 4901 Kesslersville Road Easton, PA 18040 USA +32-9-381-15-00 +32-9-380-44-38 (fax) viceuro@victaulic.be MIDDLE EAST 1-800-PICK-VIC (+1-800-742-5842) (within North America) +1-610-559-3300 +1-610-250-8817 (fax) pickvic@victaulic.com P.O.