Victron VE.Bus Configuration Guide

Table Of Contents
10. Description of Settings
10.1. General
10.1.1. System frequency setting
Alters the output frequency setting for the inverter.
10.1.2. AC1 input current limit
This setting is only active if no system panel is installed (is overruled by the remote panel if connected).
10.1.3. Current limit overruled by remote
If Overruled by remote is enabled, the input current limit can be set remotely by a GX Device or a Digital Multi Control. If not
enabled, it cannot be changed.
The use case is to typically leave it unchecked in stationary applications, as well as inputs connected to a generator, since for
them the input current limit is a static value and defined during installation.
For shore connections (boat and vehicle use) you check the box, so that the user of the system can change the input current limit
to match the shore connection they are currently using.
10.1.4. Current limit overruled by remote
Setting for use with ‘small’ generator - If an inverter-generator is used, such as the HONDA EU series, the shore current setting
will be dynamically reduced (following a period of low current consumption) to compensate for the engine reaction time when
higher loads are activated.
10.1.5. Enable Battery Monitor
Enabling the VE.Bus battery monitor, this also enables many features that can use a state of charge (SoC).
VictronConnect - VE.Bus Configuration guide
Page 10 Description of Settings