Grid code setting is not yet available in VictronConnect. Depending on the installation and regional requirements you may need to
need to use VEConfigure to adjust additional settings.
10.3. Inverter
10.3.1. Inverter output voltage
This is normally 120/230 Vac.
10.3.2. Ground Relay
Used to enable/disable the internal ground relay functionality. Connection between N and PE during inverter operation.
The ground relay is useful when an earth-leakage circuit-breaker is part of the installation. When the internal transfer switch is
open (inverter mode) the Neutral of the inverter is connected to PE. When the transfer switch closes (AC input is transferred to
the output) the Neutral is first disconnected from PE. Warning: Disabling the ground relay on "120/240V" models (split phase
models) will disconnect the L2 output from the inverter.
10.3.3. DC input low-shutdown
To set the low battery voltage level at which the inverter shuts off. To ensure long battery life, this value should be set according to
your battery manufacturer specification.
10.3.4. DC input low restart
To set the voltage at which the inverter restarts after low voltage shut-down. To prevent rapid fluctuation between shut-down and
start up, it is recommended that this value be set at least one volt higher than the low battery shut-down voltage.