EN Manual Appendix MultiPlus Compact 12 | 2000 | 80-50 120V 24 | 2000 | 50-50 120V
1. IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS! WARNING– These servicing instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions unless you are qualified to do so. General Please familiarize yourself with the safety features and instructions by first reading the documentation supplied with this product before using the equipment.
Appendix Before applying power, ensure that the available power source matches the configuration settings of the product as described in the manual. EN The installation shall be in accordance with the Canadian Electrical Code, Part 1. The wiring methods shall be in accordance with the National Electrical Code, ANSI/NFPA 70.
Ensure that the equipment is used under the correct ambient conditions. Never operate the product in a wet or dusty environment. Ensure there is adequate free space for ventilation around the product and check that the ventilation vents are not blocked. Ensure that the required system voltage does not exceed the product's capacity. Transport and Storage Ensure that the mains power and battery leads have been disconnected before storing or transporting the product.
EN 2. DESCRIPTION 2.1 General Appendix Multi Compact -functional The MultiPlus Compact gets its name from the multiple functions it can perform. It is a powerful true sine wave inverter, a sophisticated battery charger that features adaptive charge technology and a high-speed AC transfer switch in a single compact enclosure. Beside these primary functions, however, the MultiPlus Compact has several advanced features that provide a range of new applications as outlined below.
If, in order to quickly charge a battery, a high charge current in combination with a high absorption voltage has been chosen, damage due to excessive gassing will be prevented by automatically limiting the rate of voltage increase once the gassing voltage has been reached. Less maintenance and aging when the battery is not in use: the Storage mode The Storage mode kicks in whenever the battery has not been subjected to discharge during 24 hours.
EN 3. OPERATION 3.1 On/Off/Charger Only Switch Appendix When switched to "on", the product is fully functional. The inverter will come into operation and the LED "inverter on" will light up. An AC voltage connected to the "AC in" terminal will be switched through to the "AC out" terminal, if within specifications. The inverter will switch off, the "mains on" LED will light up and the charger commences charging. The "bulk", "absorption" or "float" LEDs will light up, depending on the charger mode.
3.3.3 Activating equalisation or forced absorption The MultiPlus can be put into both these states from the remote panel as well as with the front panel switch, provided that all switches (front, remote and panel) are set to “on” and no switches are set to “charger only”. In order to put the MultiPlus in this state, the procedure below should be followed. If the switch is not in the required position after following this procedure, it can be switched over quickly once.
EN 3.4 LED Indications Appendix LED off LED flashes LED illuminated Inverter inverter charger alarm on off The inverter is switched on and supplies power to the load. Battery operation. charger only inverter charger alarm on off charger only inverter charger alarm on off charger only The inverter is switched on and supplies power to the load. Pre alarm: overload, or battery voltage low, or inverter temperature high The inverter is switched off.
inverter charger on The AC input voltage is switched through and the charger operates in bulk or absorption mode. off alarm charger only inverter on The AC input voltage is switched through and the charger operates in float mode.
EN 4. INSTALLATION Appendix This product should be installed by a qualified electrician. 4.2 Location The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a clear space of at least 10cm around the appliance for cooling. The product is suitable for wall mounting. For mounting see appendix A. The appliance can be mounted horizontally as well as vertically; vertical mounting is preferable. The vertical position offers optimum cooling.
Each system requires a method of disconnecting the AC and DC circuits. If the overcurrent protection device is a circuit breaker, it will also serve as the disconnect. If fuses are used, separate disconnect switches will be needed between the source and the fuses. To reduce the risk of fire, do not connect to an ac load center (circuit breaker panel) having multiwire branch circuits connected. CAUTION – To reduce risk of injury, charge only Lead Acid or LIFEPO4 type rechargeable batteries.
PERSONAL PRECAUTIONS iii. Wear complete eye protection and clothing protection. Avoid touching eyes while working near battery. iv. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 10 min and get medical attention immediately. v. NEVER smoke or allow a spark or flame in vicinity of battery or engine. vi. Be extra cautious to reduce risk of dropping a metal tool onto battery.
• Locate marine unit away from battery in a separate, well ventilated compartment. • Never place marine unit directly above battery; gases from battery will corrode and damage marine unit. • Never allow battery acid to drip on marine unit when reading gravity or filling battery. • Do not operate marine unit in a closed-in area or restrict ventilation in any way.
Appendix Procedure Proceed as follows to connect the battery cables: EN Remark: Internal resistance is the important factor when working with low capacity batteries. Please consult your supplier or the relevant sections of our book “electricity on board”, downloadable from our website. Use an insulated box spanner in order to avoid shorting the battery. Avoid shorting the battery cables. Connect the battery cables: the + (red) on the left and the - (black) on the right, to the battery see appendix A.
4.3 Connection of the AC cabling This is a Safety Class I product (supplied with a protective grounding terminal). Uninterruptible protective grounding must be provided at the AC input and/or output terminals and/or chassis grounding point located externally on the product. The MultiPlus is provided with a ground relay (relay H, see appendix B) that automatically connects the Neutral output to the chassis if no external AC supply is available.
EN 4.4 Optional Connections 4.4.1 Second Battery The MultiPlus Compact has a connection (+) for charging a starter battery. For connection see appendix A. Appendix A number of optional connections are possible: Undo the four screws at the front of the enclosure and remove the front panel. 4.4.2 Temperature Sensor The temperature sensor supplied with the product may be used for temperaturecompensated charging. The sensor is insulated and must be mounted on the batteries minus pole.
4.4.5 Parallel Connection The MultiPlus can be connected in parallel with several identical devices. To this end, a connection is established between the devices by means of standard RJ45 UTP cables. The system (one or more Multis plus optional control panel) will require subsequent configuration (see Section 5). In the event of connecting MultiPlus units in parallel, the following requirements must be met: • A maximum of six units connected in parallel.
5.1 Standard settings: ready for use On delivery, the MultiPlus is set to standard factory values. In general, these settings are suitable for single-unit operation. Appendix Settings may only be changed by a qualified engineer Carefully read the instructions before changes are made. Batteries should be placed in a dry and well-ventilated area during charging. EN 5.
5.2 Explanation of settings Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the software configuration programs (see Section 5.3). Inverter frequency Output frequency if no AC is present at the input. Adjustability: 50Hz; 60Hz Input frequency range Input frequency range accepted by the MultiPlus. The MultiPlus synchronises within this range with the AC input frequency. The output frequency is then equal to the input frequency.
EN Appendix AES (Automatic Economy Switch) Instead of the search mode, the AES can also be chosen (with help of VEConfigure only). If this setting is turned ‘on’, the power consumption in no-load operation and with low loads is decreased by approx. 20%, by slightly 'narrowing' the sinusoidal voltage. Not adjustable with DIP switches. Applicable in stand-alone configuration only.
Bulk Protection When this setting is ‘on’, the bulk charging time is limited to 10 hours. A longer charging time could indicate a system error (e.g. a battery cell short-circuit). Not adjustable with DIP switches. AC input current limit These are the current limit settings at which PowerControl and PowerAssist come into operation. The factory setting is 30A. See Section 2, the book 'Energy Unlimited', or the many descriptions of this unique feature on our website www.victronenergy.com .
EN Appendix WeakAC Strong distortion of the input voltage can result in the charger hardly operating or not operating at all. If WeakAC is set, the charger will also accept a strongly distorted voltage, at the cost of greater distortion of the input current. Recommendation: Turn WeakAC on if the charger is hardly charging or not charging at all (which is quite rare!).
5.3 Configuration by computer All settings can be changed by means of a computer or with a VE.Net panel (except for the multi-functional relay and the VirtualSwitch when using VE.Net). Some settings can be changed with DIP switches (see Section 5.2). For changing settings with the computer, the following is required: • VEConfigure3 software: can be downloaded free of charge at www.victronenergy.com. • A MK3-USB (VE.Bus to USB) interface. Alternatively, the Interface MK2.2b (VE.
Some settings can be changed with DIP switches Appendix Procedure: a) Turn the Compact on, preferably without load and without AC voltage on the inputs. The Compact will then operate in inverter mode. b) Set the dipswitches as required. c) Store the settings by moving Dip switch 8 to “on” and back to “off”. EN 5.5 Configuration with DIP switches 5.5.1.
ds3-ds4: Setting charge voltages Absorption Time (hours) Absorption voltage Float voltage Storage Voltage 14.4 28.8 57.6 13.8 27.6 55.2 13.2 26.4 52.8 8 dS3=on dS4=off 14.1 28.2 56.4 13.8 27.6 55.2 13.2 26.4 52.8 8 dS3=off dS4=on 14.7 29.4 58.8 13.8 27.6 55.2 13.2 26.4 52.8 5 dS3=on dS4=on 15.0 30.0 60.0 13.8 27.6 55.2 13.2 26.4 52.
EN 5.5.3 Exemplary settings Example 1 is the factory setting off on off off off off off → ← Example 1: (factory setting) 1 No panel or remote switch connected 2 No panel or remote switch connected 3, 4 GEL 14.4 V 5 Frequency: 60Hz 6 Search mode off 7 AC-in Limit 30 Amp 8 store setting: off→ on→ off ds-1 ds-2 ds-3 ds-4 ds-5 ds-6 ds-7 ds-8 off on off on off off on → ← Example 2 1. No panel or remote switch connected 2. No panel or remote switch connected 3,4. AGM 14,7V 5. Frequency: 60Hz 6.
7. TROUBLE SHOOTING TABLE Proceed as follows for quick detection of common faults. DC loads must be disconnected from the batteries and the AC loads must be disconnected from the inverter before the inverter and/ or battery charger is tested. Consult your Victron Energy dealer if the fault cannot be resolved. Problem The inverter fails to operate when switched on. The inverter fails to operate Cause The battery voltage is too high or too low.
Cause The AC input voltage or frequency is out of range. The battery is overcharged. Adjust the float voltage to the correct value. The internal DC fuse is defective. The absorption voltage has been set to an incorrect value. The float voltage has been set to an incorrect value. A defective battery. Inverter is damaged. The battery is too small. Reduce the charging current or use a battery with a higher capacity. Connect a temperature sensor.
8. TECHNICAL DATA MultiPlus 12/2000/80-50 120V 24/2000/50-50 120V PowerControl / PowerAssist Yes Transfer switch (A) 50 Minimum PowerAssist current (A) 8,5 INVERTER 9,5 – 17 Input voltage range (V DC) 19 – 33 Output voltage: 120 VAC ± 2% Frequency: 60 Hz ± 0,1% (1) Output Cont. output power at 25°C (VA) (3) 2000 Cont. output power at 25°C (W) 1600 Cont.
EN Appendix 1) Can be adjusted to 50Hz 2) Protection a. Output short circuit b. Overload c. Battery voltage too high d. Battery voltage too low e. Temperature too high f. 120VAC on inverter output g.
www.victronenergy.
APPENDIX A: Connection overview A AC input line L1 and neutral (N) B 2x RJ45 connector for remote panel and/or parallel and 3-phase operation. C AC output line L1 and neutral (N). F M8 battery minus connection. G Starter battery positive (TR CHARGE). (starter battery minus: use battery minus cable for connection). H Terminals for (left to right): temperature sensor positive, temperature sensor minus. I M8 battery positive connection.
www.victronenergy.
APPENDIX C: Parallel connection APPENDIX D: Three-phase connection
www.victronenergy.
APPENDIX F: Charge curve Bulk-mode: Entered when charger is started. Constant current is applied until the gassing voltage is reached (14.4V resp. 28.8V, temperature compensated). Battery Safe Mode: If, in order to quickly charge a battery, a high charge current in combination with a high absorption voltage has been chosen, the Multi Compact / MultiPlus Compact will prevent damage due to excessive gassing by automatically limiting the rate of voltage increase once the gassing voltage has been reached.
www.victronenergy.com EN APPENDIX G: Temperature compensation Appendix Default output voltages for Float and Absorption are at 25°C. Reduced Float voltage follows Float voltage and Raised Absorption voltage follows Absorption voltage. In adjust mode temperature compensation does not apply.
www.victronenergy.
Victron Energy Blue Power Distributor: Serial number: Version : 07 Date : November 9th, 2021 Victron Energy B.V. De Paal 35 | 1351 JG Almere PO Box 50016 | 1305 AA Almere | The Netherlands General phone E-mail www.victronenergy.com : +31 (0)36 535 97 00 : sales@victronenergy.