Victron MultiPlus Compact Manual
EN
Appendix
5.5.3 Exemplary settings
Example 1 is the factory setting
ds-1
off
ds-2 Panel option
on
ds-3 Ch. voltage
off
ds-4 Ch. voltage
off
ds-5 Frequency
off
ds-6 Search mode
off
ds-7 AC-in Limit
off
ds-8 Store setting
→
←
ds-1
off
ds-2
on
ds-3
off
ds-4
on
ds-5
off
ds-6
off
ds-7
on
ds-8
→
←
ds-1
on
ds-2
off
ds-3
on
ds-4
on
ds-5
on
ds-6
on
ds-7
off
ds-8
→
←
Example 1: (factory setting)
1 No panel or remote
switch connected
2 No panel or remote
switch connected
3, 4 GEL 14.4 V
5 Frequency: 60Hz
6 Search mode off
7 AC-in Limit 30 Amp
8 store setting: off→
on→ off
Example 2
1. No panel or remote
switch connected
2. No panel or remote
switch connected
3,4. AGM 14,7V
5. Frequency: 60Hz
6. Search mode off
7. AC-in Limit 50 Amp
8. store setting: off→
on→ off
Example 3
1. Panel or remote
switch connected
2. Panel or remote
switch connected
3, 4. Tubular plate 15V
5. Frequency: 50Hz
6. Search mode on
7. AC-in Limit 30Amp
8. store setting: off→ on→
off
Store the settings (ds-3 to ds-7) by changing switch ds-8 from ‘off’ to ‘on’, and then back to
‘off’.
The LED’s ‘charger’ and ‘alarm’ will flash to indicate acceptance of the settings.
6 Maintenance
The Compact does not require specific maintenance. It will suffice to check all connections
once a year. Avoid moisture and oil/soot/vapours, and keep the device clean.