MultiPlus-II 24/3000/70-50 2x120V Manual
Table Of Contents
- MultiPlus-II 12V 3kVA 2x120V
- Table of Contents
- 1. IMPORTANT SAFETY INSTRUCTIONS - Save these instructions!
- 2. Description
- 3. Operation
- 4. Installation
- 4.1. Location
- 4.2. Connection of battery cables
- 4.3. Connection of the AC cabling
- 4.4. Optional Connections
- 4.4.1. Remote Control
- 4.4.2. Programmable relay
- 4.4.3. Programmable analog/digital input/output ports
- 4.4.4. Starter battery (connection terminal E, see appendix A)
- 4.4.5. Voltage sense (connection terminal J, see appendix A)
- 4.4.6. Temperature sensor (connection terminal J, see appendix A)
- 4.4.7. Parallel Connection
- 4.4.8. Three-phase operation
- 5. Configuration
- 6. Maintenance
- 7. Error Indications
- 8. Technical Specifications
- Appendix A. APPENDIX A: Connection overview
- Appendix B. APPENDIX B: Block diagram
- Appendix C. APPENDIX C: Parallel connection
- Appendix D. APPENDIX D: Three phase connection
- Appendix E. APPENDIX E: Charge algorithm
- Appendix F. APPENDIX F: Temperature compensation
- Appendix G. APPENDIX G: Dimensions
- Appendix H. APPENDIX H: Power flow diagrams
All of the conditions below must be met!:
1. The device is in error! (No AC output)
2. Inverter LED flashes (in opposition to any flashing of the Bulk, Absorption or Float LED)
3. At least one of the LEDs Bulk, Absorption and Float is on or flashing
Bulk LED off
Absorption LED
off flashing on
Float LED off 0 3 6
flashing 1 4 7
on 2 5 8
Bulk LED flashes
Absorption LED
off flashing on
Float LED off 9 12 15
flashing 10 13 16
on 11 14 17
Bulk LED on
Absorption LED
off flashing on
Float LED off 18 21 24
flashing 19 22 25
on 20 23 26
Bulk LED Absorption
LED Float LED
Code Meaning: Cause/solution:
1 Device is switched off because
one of the other phases in the
system has switched off.
Check the failing phase.
3 Not all, or more than, the
expected devices were found in
the system.
The system is not properly configured.
Reconfigure the system.
Communication cable error. Check the
cables and switch all equipment off, and then
on again.
4 No other device whatsoever
detected
Check the communication cables.
MultiPlus-II 12V 3kVA 2x120V
Page 22 Error Indications