MultiPlus-II 24/3000/70-50 2x120V Manual
Table Of Contents
- MultiPlus-II 12V 3kVA 2x120V
- Table of Contents
- 1. IMPORTANT SAFETY INSTRUCTIONS - Save these instructions!
- 2. Description
- 3. Operation
- 4. Installation
- 4.1. Location
- 4.2. Connection of battery cables
- 4.3. Connection of the AC cabling
- 4.4. Optional Connections
- 4.4.1. Remote Control
- 4.4.2. Programmable relay
- 4.4.3. Programmable analog/digital input/output ports
- 4.4.4. Starter battery (connection terminal E, see appendix A)
- 4.4.5. Voltage sense (connection terminal J, see appendix A)
- 4.4.6. Temperature sensor (connection terminal J, see appendix A)
- 4.4.7. Parallel Connection
- 4.4.8. Three-phase operation
- 5. Configuration
- 6. Maintenance
- 7. Error Indications
- 8. Technical Specifications
- Appendix A. APPENDIX A: Connection overview
- Appendix B. APPENDIX B: Block diagram
- Appendix C. APPENDIX C: Parallel connection
- Appendix D. APPENDIX D: Three phase connection
- Appendix E. APPENDIX E: Charge algorithm
- Appendix F. APPENDIX F: Temperature compensation
- Appendix G. APPENDIX G: Dimensions
- Appendix H. APPENDIX H: Power flow diagrams
8. Technical Specifications
MultiPlus-II 12V 3kVA 2x120V
PowerControl & PowerAssist Yes (on L1 input)
Transfer switch 50 A
Maximum AC input current 50 A (each leg)
INVERTER
DC Input voltage range 9,5 – 17 V
Output when in inverter mode Output voltage: 120 VAC ± 2%
Frequency: 60 Hz ± 0,1% (1)
Cont. output power at 25°C (3) 3000 VA
Cont. output power at 25°C 2400 W
Cont. output power at 40°C 2200 W
Cont. output power at 65°C 1700 W
Maximum apparent feed-in power 2500 VA
Peak power 5500 W
Maximum efficiency 93%
Zero load power 19 W
Zero load power in AES mode 15 W
Zero load power in Search mode 4 W
Maximum output current 60A peak, 50Arms for 1sec.
CHARGER
AC Input Split phase: 180-280 VAC 45 – 65 Hz
Single phase: 90-140 VAC 45 – 65 Hz
Charge voltage 'absorption' 14.4 V
Charge voltage 'float' 13.8 V
Storage mode 13.2 V
Maximum battery charge current (4) 120 A
Battery temperature sensor Yes
GENERAL
Auxiliary output Yes (50 A)
External AC current sensor (optional) 100 A
Programmable relay (5) Yes
Protection (2) a – g
VE.Bus communication port For parallel and three phase operation, remote monitoring
and system integration
General purpose com. port Yes, 2x
Remote on-off Yes
Operating temperature range -40 to +65°C (0 - 140°F) fan assisted cooling
Humidity (non-condensing) max 95%
ENCLOSURE
Material & Colour Steel, blue RAL 5012
Protection category IP22
Battery-connection M8 bolts
MultiPlus-II 12V 3kVA 2x120V
Page 24 Technical Specifications