CYRIXI 200A400A 12/24V AND 24/48V
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40
E-mail: sales@victronenergy.com | www.victronenergy.com
Profile 0
Connect (V)* Disconnect (V)*
Less than13V Remains open More than 12,8V Remains closed
Closes after Closes after
13V 10 min 12,8V 10 min
13,2V 5 min 12,4V 5 min
13,4V 3 min 12,2V 1 min
13,6V 1 min 12V 4 sec
13,8V 4 sec Less than 11V Immediate
INVERTER
Profile 1
Connect (V)* Disconnect (V)*
Less than 13,25V Remains open More than 12,75V Remains closed
More than 13,25V Closes after 30 sec From 10,5V to 12,75V Opens after 2 min
Less than 10,5V Immediate
Profile 2
Connect (V)* Disconnect (V)*
Less than13,2V Remains open More than 12,8V Remains closed
More than 13,2V Closes after 6 sec From 10,5V to 12,8V Opens after 30 sec
Less than 10,5V Immediate
Profile 3
Connect (V)* Disconnect (V)*
Less than13,25V Remains open More than 13,5V Remains closed
Closes after Opens after
13V 10 min 12,8V 30 min
13,2V 5 min 12,4V 12 min
13,4V 3 min 12,2V 2 min
13,6V 1 min 12V 1 min
13,8V 4 sec Less than 10,5V Immediate
NOTES
1) After connecting 3 times, the minimum time to reconnect is 1 minute (to prevent “rattling”)
2) The Cyrix will not connect if the voltage on one of the battery connections is less than 2V*. (to prevent unexpected switching during installation)
3) The Cyrix will always connect if the start assist is activated, as long as the voltage on one of the battery connections is sufficient to operate the Cyrix (approximately 10V*).
* Multiply voltage x2 for 24V systems and x4 for 48V systems