GEL AND AGM BATTERIES
www.victronenergy.com
Disadvantages of the traditional 3-step charge characteristic:
• During the bulk phase the current is kept at a constant and often high level, even after the gassing
voltage (14,34 V for a 12 V battery) has been exceeded. This can lead to excessive gas pressure in the
battery. Some gas will escape trough the safety valves, reducing service life.
• Thereafter the absorption voltage is applied during a fixed period of time, irrespective of how deep
the battery has been discharged previously. A full absorption period after a shallow discharge will
overcharge the battery, again reducing service life. (a. o. due to accelerated corrosion of the positive
plates)
• Research has shown that battery life can be increased by decreasing float voltage to an even lower
level when the battery is not in use.
11. Battery charging: longer battery life with Victron 4-step adaptive charging
Victron developed the adaptive charge characteristic. The 4-step adaptive chare curve is the result of years of
research and testing.
The Victron adaptive charge curve solves the 3 main problems of the 3 step curve:
• Battery Safe mode
In order to prevent excessive gassing, Victron has invented the ‘Battery Safe Mode’. The battery Safe
Mode will limit the rate of voltage increase once the gassing voltage has been reached. Research has
shown that this will reduce internal gassing to a safe level.
• Variable absorption time
Based on the duration of the bulk stage, the charger calculates how long the absorption time should
be in order to fully charge the battery. If the bulk time is short, this means the battery was already
charged and the resulting absorption time will also be short, whereas a longer bulk time will also
result in a longer absorption time.
• Storage mode
After completion of the absorption period the battery should be fully charged, and the voltage is
lowered to the float or standby level. If no discharge occurs during the next 24 hours, the voltage is
reduced even further and the battery goes into storage mode. The lower storage voltage reduces
corrosion of the positive plates.
Once every week the charge voltage is increased to the absorption level for a short period to
compensate for self discharge (Battery Refresh mode).
12. Battery charging in case of standby use: constant voltage float charging
When a battery is not frequently deeply discharged, a 2-step charge curve can be used. During the first phase
the battery is charged with a limited current (the bulk phase). Once a preset voltage has been reached the
battery is kept at that voltage (the float phase).
This charge method is used for starter batteries in vehicles, and in uninterruptible power supplies (UPS).
13. Optimum charge voltage of Victron VRLA batteries
The recommended charge voltage settings for a 12 V battery are shown in table 3.
14. Effect of temperature on charging voltage
The charge voltage should be reduced with increased temperature. Temperature compensation is required when the
temperature of the battery is expected to be less than 10°C / 50°F or more than 30°C / 85°F during long periods of time.
The recommended temperature compensation for Victron VRLA batteries is -4 mV / Cell (-24 mV /°C for a 12 V battery).
The centre point for temperature compensation is 20°C / 70°F.
Fig. 4: Four
-step adaptive charge curve
12
12.5
13
13.5
14
14.5
15
0
2
4
6
8
1
0
12
14
16
18
20
22
egatlov egrahC
0
20
40
60
80
100
120
tnerruc egrahC
/
/
/
/
/
/
/
/
Battery Safe Float
Battery Refresh
Storage
Figure 3:
Four-step adaptive
charge curve
Calculated absorption time
Fig. 4: Four-step adaptive charge curve