User manual
8
Cables longer then 6 m are not recommended.
Cable eyes with M6/8 holes should be used.
For supply connection use wires suitable for at least 75°C (167°F).
CAUTION: Replace defective cords or wires immediately.
Connection sequence
• Disconnect mains.
• Disconnect battery cables from the battery.
• Open front cover.
• Connect battery cables to the charger. Note that there’s only one
“minus”- Use a fuse according the size of the battery charger.
• Connect battery cables to the battery.
• Connect the AC-in by means of a 3-core cable of 2.5 – 4 mm²
flexible core to the AC-in terminal block. Note that a real PE-
connection is strictly necessary.
• Close the front panel.
Change voltage at appr. 10% of the nominal current
Absorption Float
12V 24V 12V 24V
LA
14.5 29.0 13.5 27.0
AGM
14.3 28.6 13.3 26.6
GEL
14.2 28.4 13.5 27.0
Other