Installation
2019-08-15 12:22 21/39 Color Control GX manual
Victron Energy - https://www.victronenergy.com/live/
The limit as set by the user in the CCGX will be applied to all inputs where 'Overruled by remote',
configured with VEConfigure, is enabled:
Using the example of a boat with two AC inputs and a Quattro where:
A Genset capable of delivering 50A is connected to input 1;1.
Shore power is connected to input 2. (Available power depends on the rating of the harbour2.
power-supply.)
Configure the system exactly as in above VEConfigure screenshot. Input 1 has priority over input 2,
therefore the system will automatically connect to the genset whenever it is running. The fixed input
current limit of 50A will be applied. And when the genset is not available, and mains is available on
input 2, the Quattro will use the input current limit as configured in the CCGX.
Two more examples: (In both cases if you disable 'Overrule by remote', setting a current limit in the
CCGX will have no effect. And if you enable 'Overrule by remote' for both inputs, the current limit set
in the CCGX will be applied to both inputs.)










