Installation
Last update: 2019-08-15 11:42 ccgx:start https://www.victronenergy.com/live/ccgx:start
https://www.victronenergy.com/live/ Printed on 2019-08-15 12:22
Systems where it is not possible to control the input current limit
It is not possible to control the input current limit in certain installations. In these cases, the CCGX
menu will not allow changing the setting:
Installations with a VE.Bus BMS1.
Installations with a Digital Multi Control (or its predecessors)2.
Also the on/off/charger only switch in the CCGX will be disabled in the case.
In installation with a VE.Bus BMS, use the rocker switch instead - or add a Digital Multi Control to the
installation.
Minimum input current limit values
When PowerAssist is enabled in VEConfigure, there is a minimum input current limit. The actual limit
differs for each model.
After setting the input current to a value below the limit, it will automatically be increased again to
the limit.