Cerbo GX Installation

Table Of Contents
Item Default Description
Inverter high temperature
Inverter overload
No Start on value warning - No / Yes
Start when warning is active for - seconds (to allow for
momentary spikes to pass without triggering start)
When warning is cleared stop after - seconds (to allow for
momentary dips without stopping the running generator)
Generator start/stop -> Settings -> Conditions -> Periodic run
Periodic run No Enable - No / Yes
Run interval
Skip run if has been running for
Run interval start date
Start time
Run duration (hh:mm)
Run until battery is fully charged
Generator start/stop -> Settings
Minimum run time 0 The minimum number of minutes the generator will run for any
time that it is started, even after stop conditions.
Detect generator at AC
input
No No / Yes - An alarm will be triggered when no power from the
generator is detected at the inverter AC input. Make sure that the
correct AC input is set to generator on the system setup page.
Quiet hours 0 Quiet hours will prevent normal generator run conditions from
starting the generator. It is possible for some settings to specify
override values to the quiet hours ( an extremely low battery
voltage trigger to prevent a system shutdown for example)
Reset daily run time
counters
An option to reset generator run time counters, for example if
these are used for service, or if the generator is replaced or
majorly repaired.
Generator total run time
(hours)
The total time the generator has been running since the counter
was reset.
Tank pump
Configure automatic starting and stopping of pump based on tank level(sender) information. Pump auto start/stop with Color
Control GX
Pump state Displays if the pump is running or not
Mode Auto Options are Auto, On and Off. This is the manual override to the
start and stop level triggers when a tank sensor is connected.
Tank Sensor Automatic Select the tank sensor that is used for the tank pump trigger. 'No
tank sensor' will be displayed if no tank sensor is connected or
detected,
Start level 50% The trigger point of the tank level to start the tank pump (close
the relay).
Stop level 80% The trigger point of the tank level to stop the tank pump (open
the relay).
Relay
Function Alarm relay Select the relay function. Possible functions are 'Alarm relay',
'Generator start/stop', 'Tank pump' and 'None' (disabled).
Polarity Normally open Select the polarity of the relay on the back of the Cerbo GX.
'Normally open' or 'Normally closed'. (Note that setting it to
normally closed increases the Cerbo GX power draw.)
Services
ModbusTCP Off This setting enables the ModbusTCP service. More information
about ModbusTCP in this document and in the communications
white paper https://www.victronenergy.com/upload/documents/
Whitepaper-Data-communication-with-Victron-Energy-
products_EN.pdf
Cerbo GX Manual
Page 31 Configuration